6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1644 -
No.
Phenomena
Supposed causes
Check / Confirmation
Object†
Procedure
3
Time can be
not
synchronised
with IEC103
communicati
on.
BCU does not transmit the
time synchronisation frame.
BCU
Transmit the time synchronisation
frame.
The settling of the time
synchronisation source is set
to other than IEC.
RY
Change the settling of time
synchronisation source to IEC.
Note: BCU: Bay control unit, RY: Relay
Note: The user should set “even for the parity setting. Not allowed to set except even.