Table 5-3.4 Fault indications in monitor direction
INF
Description
GI
TYP
COT
FUN(typical)
<64>
:=
start /pick-up L1
x
2
1,7,9
t(z), I, IL
<65>
:=
start /pick-up L2
x
2
1,7,9
t(z), I, IL
<66>
:=
start /pick-up L3
x
2
1,7,9
t(z), I, IL
<67>
:=
start /pick-up N
2
1,7,9
t(z), I, IL
<68>
:=
general trip
2
1,7
t(z), I, IT, IL
<69>
:=
trip L1
2
1,7
t(z), I, IT, IL
<70>
:=
trip L2
2
1,7
t(z), I, IT, IL
<71>
:=
trip L3
2
1,7
t(z), I, IT, IL
<72>
:=
trip I (back-up operation)
2
1,7
t(z)
<73>
:=
fault location X in ohms
4
1,7
t(z), I
<74>
:=
fault forward/line
2
1,7
t(z), I
<75>
:=
fault reverse/busbar
2
1,7
t(z), I
<76>
:=
teleprotection signal
transmitted
2
1,7
t(z), I
<77>
:=
teleprotection signal received
2
1,7
t(z), I
<78>
:=
zone 1
2
1,7
t(z)
<79>
:=
zone 2
2
1,7
t(z)
<80>
:=
zone 3
2
1,7
t(z)
<81>
:=
zone 4
2
1,7
t(z)
<82>
:=
zone 5
2
1,7
t(z)
<83>
:=
zone 6
2
1,7
t(z)
<84>
:=
general start/pick-up
x
2
1,7,9
t(z), I, IT, IL
<85>
:=
breaker failure
2
1,7
t(z), I
<86>
:=
trip measuring system L1
2
1,7
IT
<87>
:=
trip measuring system L2
2
1,7
IT
<88>
:=
trip measuring system L3
2
1,7
IT
<89>
:=
trip measuring system E
2
1,7
IT
<90>
:=
trip I
2
1,7
I
<91>
:=
trip I
2
1,7
I
<92>
:=
trip IN
2
1,7
I
<93>
:=
trip IN
2
1,7
I
Table 5-3.5 Auto-reclosure indications in monitor direction
INF
Description
GI
TYP
COT
FUN (typical)
<128>
:=
CB ‘on’ by AR*
1
1,7
t(z), I, IL
<129>
:=
CB ‘on’ by long-time AR*
1
1,7
t(z), I, IL
<130>
:=
AR blocked*
x
1
1,7,9
t(z), I, IL
*CB:=circuit breaker; AR:=auto-recloser