EasyManua.ls Logo

Toshiba GR200 Series - Page 1724

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1701 -
CASE 2: The case with the distance protection applied as a back-up protection with time delay
when the distance protection is applied as back-up protection the CT requirement for
GR relay can be ignored. If instantaneous tripping of distance protection is allowed
when a communication failure occurs to the current differential protection, it is
recommended that the requirement for case 1 should be applied.
<Step 1> Check the maximum through fault current I
fmaxth
I
fmaxth
< 65 X I
n
where,
I
fmaxth
: Secondary maximum through fault current
I
n
: Rated secondary current
<Step 2> Check the CT satisfies the condition given by table K-3 or K-4 depending on CT types.
Each table has 2 requirements. Both must be satisfied.
<Knee point voltage of CTs is given>
Table K-3 CT Requirement defined by V
k
Td [ms]
Requirement 1
Requirement 2
35
V
k
I
fmax
(R
ct
+ R
2
)×3
V
k
I
Lmax
(Rct+ R
2
)×14.4
50
V
k
I
fmax
(R
ct
+ R
2
)×3
V
k
I
Lmax
(Rct+ R
2
)×20
75
V
k
I
fmax
(R
ct
+ R
2
)×4
V
k
I
Lmax
(Rct+ R
2
)×28.8
100
V
k
I
fmax
(R
ct
+ R
2
)×4
V
k
I
Lmax
(Rct+ R
2
)×36.8
150
V
k
I
fmax
(R
ct
+ R
2
)×8
V
k
I
Lmax
(Rct+ R
2
)×50.4
V
k
: Knee point voltage [V]
R
ct
: Secondary CT resistance [ohms]
R
2
: Actual secondary burden [ohms]
I
fmax
: Maximum secondary fault current
I
Lmax
: Maximum
secondary load current
<Accuracy limit factor of CTs is given>
Table K-4 CT Requirement defined by n’
Td [ms]
Requirement 1
Requirement 2
35
n I
n
3.75 × I
fmax
n I
n
I
Lmax
×18
50
n I
n
3.75 × I
fmax
n I
n
I
Lmax
×25
75
n I
n
5 × I
fmax
n I
n
I
Lmax
×36
100
n I
n
5 × I
fmax
n I
n
I
Lmax
×46
150
n I
n
10 × I
fmax
n I
n
I
Lmax
×63

Table of Contents

Related product manuals