- 1705 -
<Accuracy limit factor of CTs is given>
Table K-6 CT Requirement defined by n’
n’ I
n
> Max{I
Lmax
+ I
fmin
/2, I
fmaxout
}×18
n’ I
n
≧ 3.75 × I
f_rev_max
n’ I
n
> Max{I
Lmax
+ I
fmin
/2, I
fmaxout
}×25
n’ I
n
> Max{I
Lmax
+ I
fmin
/2, I
fmaxout
}×36
n’ I
n
> Max{I
Lmax
+ I
fmin
/2, I
fmaxout
}×46
n’ I
n
> Max{I
Lmax
+ I
fmin
/2, I
fmaxout
}×63
(K-1)
n’ : Equivalent accuracy limit factor defined by the equation above.
I
n
: Secondary rated current
R
VA
: Rated secondary burden [VA]
R
ct
: Secondary CT resistance [ohms]
R
2
: Actual secondary burden [ohms]
n : Rated accuracy limit factor
I
fmax
: Maximum secondary fault current
I
f_z1_max
: Maximum secondary fault current at the zone 1 reach point
I
f_rev_max
: Maximum secondary fault current for a close-up reverse fault
I
Lmax
: Maximum
secondary load current
Max{I
Lmax
+ I
fmin
/2, I
fmaxout
}:
The larger of (I
Lmax
+ I
fmin
/2) and I
fmaxout
I
fmin
: Minimum fault current
I
fmaxout
: Maximum out-flowing fault current for the special condition
CASE 2: The case with the distance protection applied as a back-up protection with time delay
Similarly to the previous case, the condition shown in Table K-3 and Table K-4 should be
replaced by that in Table K-7 and Table K-8 respectively for “CASE 2”.