EasyManua.ls Logo

Toshiba GR200 Series - Page 252

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 229 -
energized current is smaller than the setting [OC1]. The reducing degree will be
determined with the reset curve characteristics defined in the standards.
Note: For the setting [OC1-Rtimer]=DEF (definite-time-reset), the integrated value shall
be zero when an energized current is smaller than the setting [OC1], when the
small energized current is continued for timer setting [TOC1R]. The integrated
value will not be zero when the energized current does not flow small for the
setting [TOC1R]. DEF is allowed to set in the IEEE, US, and ORG. DEF is set
unconditionally in the IEC and UK (see Table 2.15-5).
Table 2.15-4 Constants for inverse-time-reset characteristics
Curve Type
IEC 60255-151
Curve Description
kr
sec
Β
A
IEC Normal Inverse (IEC-NI)
N/A
N/A
B
IEC Very Inverse (IEC-VI)
N/A
N/A
C
IEC Extremely Inverse (IEC-EI)
N/A
N/A
-
UK Long Time Inverse (UK-LTI)
N/A
N/A
D
IEEE Moderately Inverse (IEEE-MI)
4.85
2
E
IEEE Very Inverse (IEEE-VI)
21.6
2
F
IEEE Extremely Inverse (IEEE-EI)
29.1
2
-
US CO8 inverse (US-CO8)
5.95
2
-
US CO2 short time inverse (US-CO2)
2.261
2
Figure 2.15-6 Inverse-time-reset characteristics curves
Figure 2.15-7 illustrates that an integrating value will be influenced dependent on the
DEP or DEF setting. An energized quantity (I), where I is greater than a threshold setting
[OC1], will make an integrating value, which can determine how the element operates. If the

Table of Contents

Related product manuals