EasyManua.ls Logo

Toshiba GR200 Series - Page 297

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 274 -
OCN(Function ID:443001)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
OCN2-RTMS-
US
0.010 - 50.000
-
OCN2 dependent reset time multiplier of US
inverse curve
1.000
ORG
OCN2
0.02 -
5.00
0.10 -
25.00
A
OCN2 threshold (in IDMT mode)
0.40
2.00
OCN2-DPR
10 - 100
%
OCN2 drop-out/pick-up ratio
100
OCN2-TMS-
ORG
0.010 - 50.000
-
OCN2 time multiplier of US inverse curve
1.000
OCN2-Rtimer
DEF / DEP
-
OCN2 reset delay type of ORG
DEF
TOCN2R
0.00 - 300.00
s
OCN2 definite time reset delay
0.00
OCN2-RTMS-
ORG
0.010 - 50.000
-
OCN2 dependent reset time multiplier of ORG
inverse curve
1.000
OCN2-k
0.00000 - 500.00000
-
OCN2 user original curve coefficient
0.00000
OCN2-a
0.00000 - 10.00000
-
OCN2 user original curve coefficient
0.00000
OCN2-c
0.00000 - 10.00000
-
OCN2 user original curve coefficient
0.00000
OCN2-kr
0.00000 - 500.00000
-
OCN2 user original curve coefficient
0.00000
OCN2-b
0.00000 - 10.00000
-
OCN2 user original curve coefficient
0.00000
Output
OCN2-2fBlk
Non / Block
-
OCN2 operation block by 2f-detection
Non
OCN2-VTFBlk
Non / Block
-
OCN2 operation block by VTF
Non
OCN2-CTFBlk
Non / Block
-
OCN2 operation block by CTF
Non
OCN2-UseFor
Trip / Alarm
-
OCN2 used for trip or alarm
Trip
OCN2-ARCBlk
Non / Block
-
Autoreclose block by OCN2
Block
OCN3
OCN3-Dir
NonDir / Forward /
Reverse
-
OCN3 directional characteristic
NonDir
Fwd/
OCN3-Angle
0 - 180
deg
OCN3 directional characteristic angle
45
Rev
OCN3-Vpol
0.5 - 25.0
V
OCN3 polarizing voltage level
3.0
OCN3-Timer
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
IEEE-MI / IEEE-VI /
IEEE-EI / US-CO2 /
US-CO8 / Original
-
OCN3 delay type
DT
DT
OCN3
0.02 -
50.00
0.10 -
250.00
A
OCN3 threshold (in DT mode)
0.40
2.00
OCN3-DPR
10 - 100
%
OCN3 drop-out/pick-up ratio
100
TOCN3
0.00 - 300.00
s
OCN3 operating delay time
1.00
IEC
OCN3
0.02 -
5.00
0.10 -
25.00
A
OCN3 threshold (in IDMT mode)
0.40
2.00
OCN3-DPR
10 - 100
%
OCN3 drop-out/pick-up ratio
100
OCN3-TMS-
IEC
0.010 - 50.000
-
OCN3 time multiplier of IEC inverse curve
1.000
TOCN3R
0.00 - 300.00
s
OCN3 definite time reset delay
0.00
UK
OCN3
0.02 -
5.00
0.10 -
25.00
A
OCN3 threshold (in IDMT mode)
0.40
2.00
OCN3-DPR
10 - 100
%
OCN3 drop-out/pick-up ratio
100
OCN3-TMS-
UK
0.010 - 50.000
-
OCN3 time multiplier of UK inverse curve
1.000
TOCN3R
0.00 - 300.00
s
OCN3 definite time reset delay
0.00
IEEE
OCN3
0.02 -
5.00
0.10 -
25.00
A
OCN3 threshold (in IDMT mode)
0.40
2.00
OCN3-DPR
10 - 100
%
OCN3 drop-out/pick-up ratio
100
OCN3-TMS-
IEEE
0.010 - 50.000
-
OCN3 time multiplier of IEEE inverse curve
1.000
OCN3-Rtimer
DEF / DEP
-
OCN3 reset delay type of IEEE
DEF
TOCN3R
0.00 - 300.00
s
OCN3 definite time reset delay
0.00