6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 375 -
EFCTF
&
1
OVGCTF
8000001C23
8100001C27
CTF-EN
OPT-On
&
&
1
CB_ALLPH_CLOSE
0.02s
CTF_BLOCK
800000EBB0
1
8100001B60
EXTERNAL_CTF
810000EBB1
1
8000001B62
CTF_DETECT
t 0
10.0s
8000001B61
CTF_ALARM
On
From PROT-CCOMMON
1
1
PSBS-VCTF-BLK
From DISTANSE-ZS
2
PSBG-VCTF-BLK
From DISTANSE-ZG
2
1
AMF_OFF
From test
4
1
1
To EF
3
To BCD
3
To OCN
3
8100001BB1
t 0
0.015s
S
R
1
t 0
0.1s
1
To Automatic supervision
1
Figure 2.31-1 Scheme logic in the CTF function
1
Note: Signal CB_ALLPH_CLOSE is provided from Protection common function
(PROT_COMMON). For more information, see Chapter
Relay application:
Protection common
.
2
Note: Entering signals come from distance protections (ZS/ZG) when the ZS/ZG are
available in the IED. For more information, see Chapter
Relay application:
Distance protection
.
3
Note: Output signals are provided for respective relays when the relays are available.
See
Appendix: Ordering
whether the relays are supplied into the IED.
4
Note: AMF feature is used for the test. To generate the AMF signal, see chapter
User
interface: test-submenu
.
If a PLC signal is injected at the PLC connection point CTF_BLOCK, the operation of
the CTF function is blocked. The user can program to inject an external signal for the failure
detection using the PLC connection point EXTERNAL_CTF; the CTF_DETECT signal is
generated when the signal is injected at the EXTERNAL_CTF.