6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 425 -
stage, which the ARC issues a three-phase trip signal (CB1_94TT or CB2_94TT) for the TRC
function; the ARC function abandons to reclose the CB#1 and CB#2 (ARC1 FT or ARC2 FT).
CB is not ready for ARC operation
Failure to issue ARC shot
ARC block command has come through PLC connection points
Multi-phase trip in SPAR mode
Evolving fault (single phase to multiphase) in SPAR and TPAR mode
No link within parallel lines in MPAR mode; ( final trip selected)
Final trip selected for 3-phase fault (user settable)
ARC close fail
Shot number over