- 448 -
ARC1 and ARC2 functions being generating ARC1 IN-PROG OR or ARC2-S1 IN-PROG
signals. The switch [FT-3P FAULT] requires signals of the external relay; PLC connection
points RYOP-A, RYOP-B, and RYOP-C are used to get the signals.
Note that the CB1_94TT and CB2_94TT signals are generated when ARC BLOCK
signals are injected, provided ARC1 IN-PROG OR or ARC2-S1 IN-PROG signals is being
generated.
If, with regard to the tripped poles of CBs, there is not consistency between the CB#1 and
the CB#2, the ARC function can generate the CB1_94TT and CB2_94TT signals when an
external device is able to detect the consistency; use PLC connection points F.CB1_94TT and
F.CB2_94TT for the operation of the inconsistency.
The Start logic can receive a stop signal not to operate the ARC function; use PLC
connection point ARC NO ACT.