- 448 - 
 
ARC1  and  ARC2  functions  being  generating  ‘ARC1  IN-PROG  OR’  or  ‘ARC2-S1  IN-PROG’ 
signals.  The  switch  [FT-3P  FAULT]  requires  signals  of  the  external  relay;  PLC  connection 
points ‘RYOP-A, RYOP-B, and RYOP-C’ are used to get the signals. 
 
Note  that the ‘CB1_94TT’  and ‘CB2_94TT’ signals  are  generated  when ‘ARC BLOCK’ 
signals are injected, provided ‘ARC1 IN-PROG OR’ or ‘ARC2-S1 IN-PROG’ signals is being 
generated. 
 
If, with regard to the tripped poles of CBs, there is not consistency between the CB#1 and 
the CB#2, the ARC function can generate the ‘CB1_94TT’ and ‘CB2_94TT’ signals when an 
external device is able to detect the consistency; use PLC connection points ‘F.CB1_94TT’ and 
‘F.CB2_94TT’ for the operation of the inconsistency. 
 
The  Start  logic  can  receive  a  stop  signal  not  to  operate  the  ARC  function;  use  PLC 
connection point ‘ARC NO ACT’.