EasyManua.ls Logo

Toshiba GR200 Series - Page 511

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 488 -
When VCHK1 and VCHK2 are used in 1.5CB system, set the scheme switches [SYN-
VBus], [SYN-VLine], and [SYN-VLine2]. For example, the settings in Figure 2.35-9 are applied
when VCHK 1 and VCHK2 are applied in the 1.5CB system.
Table 2.35-10 Setting example for 1.5CB system
Output voltage
at VT
Bus-bar VT= Phase-B
Line VT= Three phase
Line2 VT= Phase-B
Input voltage
at VCT
Running voltage of SYN1(V
S
)=Phase-B (Bus-bar VT)
Incoming voltage of SYN1 and SYN2 (V
b
)=Phase-B (Line VT)
Running voltage of SYN2 (V
S2
)= Phase-B (Line2 VT)
VCHK Setting
3
[SYN-VBus] = V3
[SYN-VLine]= V-L2
[SYN-VLine2] = V4
3
Note: Set V-L2 for the scheme switch [SYN-VLine]. This is because V3 and V
L2
are in
the same phase. Set V4 for the scheme switch [SYN-VLine2]. This is because V3
and V4 are in the same phase.
Table 2.35-11 VCHK line1 and line2 selection setting
Scheme switch
Set
Comment
SYN-VBus
V-L1 / V-L2 / V-L3 / V-L12 / V-L23 /
V-L31 / V2-L1 / V2-L2 / V2-L3 / V2-
L12 / V2-L23 / V2-L31 / V3 / V4
Selection of Bus
voltage(Running Voltage) for
SYN1
SYN-VLine
V-L1 / V-L2 / V-L3 / V-L12 / V-L23 /
V-L31 / V2-L1 / V2-L2 / V2-L3 / V2-
L12 / V2-L23 / V2-L31 / V3 / V4
Selection of Line voltage
(Incoming Voltage) for SYN1
and SYN2
SYN-VLine2
V-L1 / V-L2 / V-L3 / V-L12 / V-L23 /
V-L31 / V2-L1 / V2-L2 / V2-L3 / V2-
L12 / V2-L23 / V2-L31 / V3 / V4
Selection of Line2 voltage
(Running voltage) for SYN2