6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 593 -
GCNT01 function (Function ID: 54001)
GCNT01_SLD_CSCN
(540001 8A0E011E76)
GCNT01_CMM_REQ
Command Remote-Reset-Control
Either SBO mode or DIR mode
(e.g., “ctlmodel” in IEC61850*)
In SBO operate
In DIR operate
Select Failed
540001 700E016D09
To BO connection
Input
Output
Select logic in GCNT01
0.2s
0
t
0.3s
0
t
&
&
&
Complete
Automatic sequence control function (AQEQ)§ in progress
ASEQ_MULTI_SEL
Select condition
1
Select command
Operate command
For SBO operation
For DIR operation
To Wait for a command
To Wait for a next
command
GCNT01_SLF_CSCN
(540001 8B0E011E7B)
Figure 3.7-6 Select ‘Reset’ in GCNT01
††
Note: A select condition signal is provided from the select condition logic. For more
information, see Figure 3.7-7.
§Note: An automatic sequence control (ASEQ) function can provide sequential signals for
automatic control. The GCNT01 operation is blocked for the ASEQ function when
it is in operation. For more information on the ASEQ function, see Chapter
Control and monitoring application: Automatic sequence control function
.
*Note: The GNCT01 function can run in either the SBO mode or the DIR mode using
a signal called ctlmodel when communication is implemented using IEC61850.
To use this signal, the user should map it for IEC61850 communication.
††
Note: To identify the input and output points of the other GCNT02GCNT32 logics, see
Table 3.7-2 for the inputs and Table 3.7-5 for the outputs.