6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 822 -
Signal monitoring points
SYNDIF (Function ID: 560001)
Element ID
Name
Description
850B021F59
SYNC02_SYN_CLC
SYNC DEV2 synchronism close command
Connection points in PLC logic
SYNCHK (Function ID: 560001)
Element ID
Name
Description
800B01EDEA
SYNC01_DDV_CL_ECP
SYNC DEV1 27Vr & 27Vi close enable condition signal from PLC
800B01EDE9
SYNC01_DLV_CL_ECP
SYNC DEV1 27Vr & 84Vi close enable condition signal from PLC
800B01EDE8
SYNC01_LDV_CL_ECP
SYNC DEV1 84Vr & 27Vi close enable condition signal from PLC
800B01EDE7
SYNC01_LLV_CL_ECP
SYNC DEV1 84Vr & 84Vi close enable condition signal from PLC
800B01EDE6
SYNC01_LPS_CL_ECP
SYNC DEV1 loop synchronism close enable condition signal from PLC
800B01EDED
SYNC01_RY1_USE_STS
SYNC DEV1 Relay Module1 use status from PLC
800B01EDEE
SYNC01_RY2_USE_STS
SYNC DEV1 Relay Module2 use status from PLC
800B01EDEB
SYNC01_SBK_CSP
SYNC DEV1 synchronism block condition signal from PLC
800B01EDE0
SYNC01_SBP_ECP
SYNC DEV1 synchronism bypath enable condition signal from PLC
800B01EDE1
SYNC01_SBP_SSP
SYNC DEV1 synchronism bypath success condition signal from PLC
800B01EDE4
SYNC01_SCL_CSP
SYNC DEV1 synchronism close condition signal from PLC
800B01EDE2
SYNC01_SCL_F_ECP
SYNC DEV1 synchronism close fail condition signal from PLC
800B01EDE3
SYNC01_SCL_SSP
SYNC DEV1 synchronism close success condition signal from PLC
800B01EDE5
SYNC01_SPS_CL_ECP
SYNC DEV1 split SYNC. close enable condition signal from PLC
800B01EDEC
SYNC01_SS_VCS_PLC
SYNC DEV1 success voltage condition signal from PLC
800B02EDEA
SYNC02_DDV_CL_ECP
SYNC DEV2 27Vr & 27Vi close enable condition signal from PLC
800B02EDE9
SYNC02_DLV_CL_ECP
SYNC DEV2 27Vr & 84Vi close enable condition signal from PLC
800B02EDE8
SYNC02_LDV_CL_ECP
SYNC DEV2 84Vr & 27Vi close enable condition signal from PLC
800B02EDE7
SYNC02_LLV_CL_ECP
SYNC DEV2 84Vr & 84Vi close enable condition signal from PLC
800B02EDE6
SYNC02_LPS_CL_ECP
SYNC DEV2 loop synchronism close enable condition signal from PLC
800B02EDED
SYNC02_RY1_USE_STS
SYNC DEV2 Relay Module1 use status from PLC
800B02EDEE
SYNC02_RY2_USE_STS
SYNC DEV2 Relay Module2 use status from PLC
800B02EDEB
SYNC02_SBK_CSP
SYNC DEV2 synchronism block condition signal from PLC
800B02EDE0
SYNC02_SBP_ECP
SYNC DEV2 synchronism bypath enable condition signal from PLC
800B02EDE1
SYNC02_SBP_SSP
SYNC DEV2 synchronism bypath success condition signal from PLC
800B02EDE4
SYNC02_SCL_CSP
SYNC DEV2 synchronism close condition signal from PLC
800B02EDE2
SYNC02_SCL_F_ECP
SYNC DEV2 synchronism close fail condition signal from PLC
800B02EDE3
SYNC02_SCL_SSP
SYNC DEV2 synchronism close success condition signal from PLC
800B02EDE5
SYNC02_SPS_CL_ECP
SYNC DEV2 split SYNC. close enable condition signal from PLC
800B02EDEC
SYNC02_SS_VCS_PLC
SYNC DEV2 success voltage condition signal from PLC

Table of Contents