- 867 - 
 
DPOS01  function  (Function  ID:  512001) 
Operate Cmd.   
with ILK† condition 
Operation Cmd.   
without ILK† condition 
Command “Remote-Off-Control” 
ILK† condition (“OFF”) passed 
ASEQ function§” is in progress 
User configurable condition 
(PLC#3 connection point) 
  “DPOS01_FEC_OK_CSF” 
(512001 8003011E7E) 
  “DPOS01_FEX_BO” §§ 
(512001 8103011DD0) 
  “DPOS01_EX_FFL” 
(512001 8603011E91) 
  “DPOS01_FEC_OK_CS” 
(512001 8003011E81) 
Detection of state-change in a device 
User configurable condition 
(PLC#2 connection point) 
  “DPOS01_EX_CMP” 
(512001 8003011E93) 
 
Figure 4.8-22 Operate Off from the remote-end in DPOS01
††
 
†Note: The ILK function can provide the operation criteria for “Off”. 
‡Note: An “operate condition” signal is generated in the operate-condition logic (see 
Figure 4.8-31), when Fixlogic is set for scheme switch [DPOS01-LGCTRCON]. If 
an alternative “operate-condition” is required, it can be programmed by the user 
and used to replace the signal generated by the original operate-condition logic. 
The alternative “operate-condition” can be connected to the above logic using 
connection point #3 “User-configurable condition”. That is set the [DPOS01-
LGCTRCON] to PLC and use “DPOS01IN_TMP_34”. 
§Note: The ASEQ function can provide sequential signals for automatic control. 
§§Note: The “DPOS01_OEX_BO” signal is issued when Fixedlogic is set for scheme 
switch [DPOS01-LGCFEXOT]. The “Operate completed” signal can also be issued 
from logic programmed by the user in place of the logic shown in Figure 4.8-20. 
The user programmed logic is connected internally to the signal “Operate 
completed”, hence this signal is now generated the user-programmed logic at 
connection point #2 “User-configurable condition”. That is, set the scheme switch 
[DPOS01-LGCFEXOT] to PLC and use “DPOS01IN_TMP_42”. 
*Note: The user can select a type of output signal. When Var is set for scheme switch 
[DPOS01-PLSM], the output period of the signal is defined by the setting 
[DPOS01-CPW]. When Fix is set, the signal ceases when the 43-switch is changed.