6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1051 -
Table 5.4-4 Setting items for binary input circuits in the variable type (i.e., BI2A module)
Setting devices
Range
Units
Contents
Default
Common
BI1-3_PICKUP
18 to 222
V
Guaranteed-minimum-pick-ups at BI1, BI2, and BI3
77
BI4-6_PICKUP
18 to 222
V
Guaranteed-minimum-pick-ups at BI4, BI5, and BI6
77
BI7-9_PICKUP
18 to 222
V
Guaranteed-minimum-pick-ups at BI7 to BI9
77
BI10-12_PICKUP
18 to 222
V
Guaranteed-minimum-pick-ups at BI10 to BI12
77
CMP_NUM
4 to 9
Number of times in the filter
4
BI1_CPL
Off/On
Switch for programmable operation in BI1
Off
BI1
On Delay Timer
0.000 to 300.000
s
Value in the on-delay timer
0.000
Off Delay Timer
0.000 to 300.000
s
Value in the off-delay timer
0.000
INVERSE-SW
Normal / Inverse
Inversion operation of BI1 signal
Normal
BI2_CPL
Off/On
Switch for programmable operation in BI 2
Off
BI2
On Delay Timer
0.000 to 300.000
s
Value in the on-delay timer
0.000
Off Delay Timer
0.000 to 300.000
s
Value in the off-delay timer
0.000
INVERSE-SW
Normal / Inverse
Inversion operation of BI2 signal
Normal
BI3_CPL
Off/On
Switch for programmable operation in BI 3
Off
BI3
On Delay Timer
0.000 to 300.000
s
Value in the on-delay timer
0.000
Off Delay Timer
0.000 to 300.000
s
Value in the off-delay timer
0.000
INVERSE-SW
Normal / Inverse
Inversion operation of BI3 signal
Normal
..
..
..
..
..
BI
n
_CPL
Off/On
Switch for programmable operation in BI
n
Off
BI
n
4
On Delay Timer
0.000 to 300.000
s
Value in the on-delay timer
0.000
Off Delay Timer
0.000 to 300.000
s
Value in the off-delay timer
0.000
INVERSE-SW
Normal / Inverse
Inversion operation of BIn signal
Normal
4
Note: BI1_CPL~BI12_CPL settings are provided for the BI2A module.
As an example, Figure 5.4-1 shows the binary input circuit of the BI1A in order to help
understand the settings. The BI1A consists of 18 binary input circuits and each circuit has
three settings:
Setting threshold level
Comparison feature for contact chatter
CPL switches (Delayed pick-up and delayed drop-off signal and Logic level
inversion), used as basis of input signal characteristics.