EasyManua.ls Logo

Toshiba GR200 Series - Page 117

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 94 -
impedance and negative-sequence impedance are the same and that the influences of the fault
resistance are ignored.
(2.10-7)
(2.10-8)

(2.10-9)
where,
V
1
: Relay point positive-sequence voltage
V
2
: Relay point negative-sequence voltage
V
0
: Relay point zero-sequence voltage
V
1
F: Fault point positive-sequence voltage
V
2
F: Fault point negative-sequence voltage
V
0
F: Fault point zero-sequence voltage
I
1
: Relay point positive-sequence current
I
2
: Relay point negative-sequence current
I
0
: Relay point zero-sequence current
I
0
m: Adjacent line zero-sequence current
Z
1
: Fault point - relay point positive-sequence impedance
Z
0
: Fault point - relay point zero-sequence impedance
Z
0
m: Adjacent line zero-sequence mutual impedance
Considering the faulted phase voltage V
a
F at the point of fault is,

(2.10-10)
Phase-A voltage V
a
at the relay is calculated from the following equation:



(2.10-11)
Where, I
a
is the current of phase-A at the relay and is defined in the following equation
by the symmetrical component of the current:
(2.10-12)
Here, defining the current synthesized using the phase-A current at the relay as I
a
', and
󰆒
󰇛
󰇜


(2.10-13)
Then equation (2.10-11) can be re-written in the following form:

Table of Contents

Related product manuals