EasyManua.ls Logo

Toshiba GR200 Series - Page 124

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 101 -
= lagging angle of I to Vp
θ = directional angle setting
θ
X
R
o
lagging
Quad element
I
Directional element
Figure 2.10-9 Directional element
For the element for the fault in phase-bc, the polarizing voltage (Vp
bc
) is given using
Equation (2.10-29):


󰇛

󰇜


(2.10-29)
For the element for the fault in phase-a, the polarizing voltage (Vp
a
) is given using
Equation (2.10-30):

󰇛

󰇜


(2.10-30)
where,
V
0
= voltage in zero-sequence
Va = voltage in phase-A
Vbc = voltage in phase-bc
In Equation (2.10-29), the Vp
bc
voltage is subject to the memory action if the close-in
fault occurs in three-phases; that is, the values of the Va and Vbc voltages are set from the pre-
fault voltages. The memory is retained for two cycles after the fault occurs. Note that the
polarizing voltage (Vpa) in Equation (2.10-30) is not subject to the memory action.
If a close-in fault in three-phases occurs, the Quad element can be enhanced for an offset
Quad element, as shown in Figure 2.10-10. Similar to issuing the instantaneous trip signal for
the close-in three-phase fault, this enables the Quad element to issue a trip signal with a
delayed time together using the memory action.

Table of Contents

Related product manuals