- 1677 -
Functional Data (1/7)
Phase-segregated Current Differential Protection
DIFI1 (Small current region)
0.10 to 2.00A in 0.01A steps (1A rating)
0.50 to 10.00A in 0.01A steps (5A rating)
DIFI2 (Large current region)
0.6 to 60.0A in 0.1A steps (1A rating)
3.0 to 300.0A in 0.1A steps (5A rating)
DIFL-Slope1 (Small current region)
DIFL-Slope2 (Large current region)
0.00 to 100.00s in 0.01s steps
Less than 1 cycle at 300% of DIFI1
Less than 110 ms (for tripping output)
Less than 40 ms (for signal output)
Zero-sequence Current Differential Protection for high-resistance earth
0.05 to 1.00A in 0.01A steps (1A rating)
0.25 to 5.00A in 0.01A steps (5A rating)
0.00 to 300.00s in 0.01s steps
Charging Current Compensation
0.00 to 1.00A in 0.01A steps (1A rating)
0.00 to 5.00A in 0.01A steps (5A rating)
Differential Current Supervision
0.05 to 2.00A in 0.01A steps (1A rating)
0.25 to 10.00A in 0.01A steps (5A rating)
0.02 to 50.00A in 0.01A steps (1A rating)
0.10 to 250.00A in 0.01A steps (5A rating)
Rate of Overcurrent change threshold
0.05 to 0.20A in 0.01A steps (1A rating)
0.25 to 1.00A in 0.01A steps (5A rrating)
Phase sequence Undervoltage threshold
5.0 to 130.0V in 0.1V steps
Phase to Phase Undervoltage threshold
5.0 to 130.0V in 0.1V steps
Rate of voltage change threshold
DIFG Guard characteristic
Rate of Earth fault change threshold
0.02 to 50.00A in 0.01A steps (1A rating)
0.10 to 250.00A in 0.01A steps (5A rating)