- 1678 -
Functional Data (2/7)
Phase Fault Distance Measuring Element
Z*-Mho.Reach, Z*-X.Reach and Z*-R.Reach
(Z1S, Z1XS, Z2S, Z3S, Z4S, Z5S, ZCSF,
ZCSR))
0.10 to 500.00Ω in 0.01Ω steps (1A rating)
0.01 to 100.00Ω in 0.01Ω steps (5A rating)
Characteristic angle
Z*-Mho.Angle and Z*-R.Angle (Z1S, Z1XS,
Z2S, Z3S, Z4S, Z5S, ZCSF, ZCSR))
Z*- DirX.Angle and Z*-DirR.Angle ((Z1S,
Z1XS, Z2S, Z3S, Z4S, Z5S, ZCSF, ZCSR))
ZSF-X.GrAngle1 and ZSR-X.GrAngle1
ZSF-X.GrAngle2 and ZSR-X.GrAngle2
Trip time characteristics (IEC60255-121)
Earth Fault Distance Measuring Element
Z*-Mho.Reach, Z*-X.Reach and Z*-R.Reach
((Z1G, Z1XG, Z2G, Z3G, Z4G, Z5G, ZCGF,
ZCGR)
0.10 to 500.00Ω in 0.01Ω steps (1A rating)
0.01 to 100.00Ω in 0.01Ω steps (5A rating)
Characteristic angle
Z*-Mho.Angle and Z*-R.Angle (Z1G, Z1XG,
Z2G, Z3G, Z4G, Z5G, ZCGF, ZCGR)
Z*- DirX.Angle and Z*-DirR.Angle (Z1G,
Z1XG, Z2G, Z3G, Z4G, Z5G, ZCGF, ZCGR)
ZGF-X.GrAngle1 and ZGR-X.GrAngle1
ZGF-X.GrAngle2 and ZGR-X.GrAngle2
Trip time characteristics (IEC60255-121)
Time setting of Z1S, Z1XS, Z2S, Z3S, Z4S,
Z5S, Z1G, Z1XG, Z2G, Z3G, Z4G, Z5G
0.00 to 100.00s in 0.01steps
Overcurrent Element for Fail-safe
Overcurrent elements Z*_OCFS for
supervision distance measuring elements
((Z1S, Z1XS, Z2S, Z3S, Z4S, Z5S, Z1G, Z1XG,
Z2G, Z3G, Z4G, Z5G)
0.02 to 5.00A in 0.01A steps (1A rating )
0.10 to 25.00A in 0.01A steps (5A rating)