- 1679 -
Functional Data (3/7)
Command Protection Distance Scheme
Time for current reverse block
0.00 to 10.00s in 0.01s steps
Coordination time for BOP scheme
0.00 to 1.00s in 0.01s steps
Command Protection Earth Fault Scheme
0.00 - 0.30s in 0.01s steps
Time for current reverse block
0.00 to 10.00s in 0.01s steps
Coordination time for BOP scheme
0.00 to 1.00s in 0.01s steps
Detection zone (PSBGS)
Detection timer (TPSBS)
2.50 to 75.00Ω in 0.01Ω steps (1A rating)
0.50 to 15.00Ω in 0.01Ω steps (5A rating)
Minimum load resistance (LESR, LESL)
0.10 to 500.00Ω in 0.01Ω steps (1A rating)
0.01 to 100.00Ω in 0.01Ω steps (5A rating)
Maximum load angle (LESR-Angle, LESL-
Angle)
Charging Current Compensation
Charging current compensation for distance
relay
0.00 to 1.00A in 0.01A steps (1A rating)
0.00 to 5.00A in 0.01A steps (5A rating)
Rated voltage for charging current
compensation
Minimum Operating Current
0.08A fixed (1A relay)
0.4A fixed (5A relay)
0.10 to 1.00A in 0.01A steps(1A rating)
0.50 to 5.00A in 0.01A steps (5A rating)
Switch-on-to-fault Protection
0.02 to.5.00A in 0.01A steps (1A rating)
0.10 to 15.00A in 0.01A steps (5A rating)
0.02 to 5.00A in 0.01A steps (1A rating)
0.10 to 15.00A in 0.01A steps (5A rating)
Out-of-step Protection (Out of step tripping (voltage phase comparison)
OFF / TRIP / BO(separated from other trip signals)
Out-of-step Protection (impedance locus)
Resistive reach (at Right side)
15.00 to 150.00Ω in 0.01Ω steps (1A rating)
3.000 to 30.000Ω in 0.01Ω steps (5A rating)
Resistive reach (at Left side)
5.00 to 50.00Ω in 0.01Ω steps (1A rating)
1.000 to 10.000Ω in 0.01Ω steps (5A rating)
Resistive reach (at Forward)
5.00 to 250.00Ω in 0.01Ω steps (1A rating)
1.000 to 50.000Ω in 0.001Ω steps (5A rating)
Resistive reach (at Backward)
1.0 to 50.00Ω in 0.01Ω steps (1A rating)
0.200 to 10.000Ω in 0.001Ω steps(5A rating)
0.01 to 1.00s in 0.01s steps