6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1680 -
Functional Data (4/7)
Breaker Failure (BF) Protection
Overcurrent element
0.1 to 2.0A in 0.1A steps (1A rating)
0.5 to 10.0A in 0.1A steps (5A rating)
BF timer for retry-trip of failed breaker
50 to 500ms in 1ms steps
BF timer for related breaker trip
50 to 500ms in 1ms steps
Non-directional and Directional Overcurrent Protection
1
st
, 2
nd
, 3
rd
, 4
th
Definite time overcurrent
threshold
0.02 to 50.00A in 0.01A steps (1A rating)
0.10 to 250.00A in 0.01A steps (5A rating)
1
st
, 2
nd
, 3
rd
, 4
th
Inverse time overcurrent
threshold
0.02 to 5.00A in 0.01A steps (1A rating)
0.10 to 25.00A in 0.01A steps (5A rating)
Direction characteristic
Polarising voltage
Non Directional / Forward / Backward
1.0 V(fixed)
Characteristic angle
0 180 deg in 1 deg steps
Delay type
DT / IEC-NI / IEC-VI / IEC-EI / UK-LTI / IEEE-MI / IEEE-
VI / IEEE-EI / US-CO2 / US-CO8 / Original
Drop-out/pick-up ratio
10 to 100% in 1% steps
DTL delay
0.00 to 300.00s in 0.01s steps
IDMTL Time Multiplier Setting TMS
0.010 to 50.000 in 0.001 steps
Reset type
Definite Time or Dependent Time
Reset definite delay
0.00 to 300.00s in 0.01s steps
Reset Time Multiplier Setting RTMS
0.010 to 50.000 in 0.001 steps
Non-directional and Directional Earth Fault Protection
1
st
, 2
nd
, 3
rd
, 4
th
Definite time earth fault
threshold
0.02 to 50.00A in 0.01A steps (1A rating)
0.10 to 250.00A in 0.01A steps (5A rating)
1
st
, 2
nd
, 3
rd
, 4
th
Inverse time earth fault
threshold
0.02 to 5.00A in 0.01A steps (1A rating)
0.10 to 25.00A in 0.01A steps (5A rating)
Direction characteristic
Non Directional / Forward / Backward
Characteristic angle
0 to 180° in 1° steps (3I0 lags for −3V0)
Polarising voltage (3V0)
0.5 to 100.0V in 0.1V steps
Delay type
DT / IEC-NI / IEC-VI / IEC-EI / UK-LTI / IEEE-MI / IEEE-
VI / IEEE-EI / US-CO2 / US-CO8 / Original
Drop-out/pick-up ratio
10 to 100% in 1% steps
DTL delay
0.00 to 300.00s in 0.01s steps
IDMTL Time Multiplier Setting TMS
0.010 to 50.000 in 0.001 steps
Reset type
Definite Time or Dependent Time
Reset definite delay
0.00 to 300.00s in 0.01s steps
Reset Time Multiplier Setting RTMS
0.010 to 50.000 in 0.001 steps