6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 163 -
ZG (Function ID 431001
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
Z1G-EN
Off / On
-
Z1G protection enable
Off
Z2G-EN
Off / On
-
Z2G protection enable
Off
Z3G-EN
Off / On
-
Z3G protection enable
Off
Z4G-EN
Off / On
-
Z4G protection enable
Off
Z5G-EN
Off / On
-
Z5G protection enable
Off
Z1XG-EN
Off / On
-
Z1XG protection enable
Off
Comm.
ZG-Chara
Quad / Mho
-
ZG relay characteristic
Quad
ZGF-
X.GrAngle1
0 - 45
deg
ZG-forward gradient characteristic angle (for
Quad and Mho-X)
0
ZGF-
X.GrAngle2
45 - 90
deg
ZG-forward gradient characteristic angle (for
Quad and Mho-X)
60
PSB
PSBGZ
2.50 -
75.00
0.50 -
15.00
-
Power swing block detection
10.00
2.00
TPSBG
0.020 - 0.100
s
Power swing block detection timer
0.040
PSBGFR
Off / On
-
Power swing block reset enable
Off
TPSBGFR
0.00 - 10.00
s
Power swing block reset timer
1.00
LEG
LEGR
0.10 -
500.00
0.01 -
100.00
-
Minimum load resistance on the right
25.50
5.10
LEGR-Angle
5 - 75
deg
Maximum load angle on the right
10
LEGL
0.10 -
500.00
0.01 -
100.00
-
Minimum load resistance on the left
25.50
5.10
LEGL-Angle
5 - 75
deg
Maximum load angle on the left
10
EFL
EFL
0.10 - 1.00
0.50 -
5.00
A
EFL threshold
0.20
1.00
UVPWI
ZG-UVPWI-EN
Off / On
-
UV for positive weak infeed
Off
UVPWI
5.0 - 130.0
V
UVPWI relay operation level
30.0
Z1G
Z1G-Dir
Forward / Reverse /
NonDir
-
Z1G direction to protect
Forward
Mho
Z1G-Mho.Angle
30 - 90
deg
Z1G mho characteristic angle (for Mho)
85
Z1G-
Mho.Reach
0.10 -
500.00
0.01 -
100.00
-
Z1G mho reach (for Mho)
8.00
1.60
Z1G-MhoX.EN
Off / On
-
Z1G reactance reach use or not (for Mho)
Off
Z1G-X.Reach
0.10 -
500.00
0.01 -
100.00
-
Z1G reactance reach
8.00
1.60
Z1G-MhoR.EN
Off / On
-
Z1G resistive reach use or not (for Mho)
Off
Z1G-R.Angle
30 - 90
deg
Z1G resistive reach characteristic angle
75
Z1G-R.Reach
0.10 -
500.00
0.01 -
100.00
-
Z1G resistive reach
25.50
5.10
Z1G-
MhoDX.EN
Off / On
-
Z1G directional-X characteristic use or not (for
Mho)
Off
Z1G-DX.Angle
0 - 60
deg
Z1G directional-X characteristic angle
30
Quad
Z1G-X.Reach
0.10 -
500.00
0.01 -
100.00
-
Z1G reactance reach
8.00
1.60
Z1G-
X.GrAngleEN
Off / On-Set / On-
Adapt
-
ZG gradient characteristic
Off
Z1G-R.Angle
30 - 90
deg
Z1G resistive reach characteristic angle
75
Z1G-R.Reach
0.10 -
500.00
0.01 -
100.00
-
Z1G resistive reach
25.50
5.10
Z1G-DX.Angle
0 - 60
deg
Z1G directional-X characteristic angle
30
Z1G-DR.Angle
0 - 60
deg
Z1G directional-R characteristic angle (for
Quad)
5
I0K
Z1G-Krs
0 - 1000
%
Zero phase current factor, Self line R0/R1
100
Z1G-Kxs
0 - 1000
%
Zero phase current factor, Self line X0/X1
100