6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 237 -
OC (Function ID: 440001)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
TOC2R
0.00 - 300.00
s
OC2 definite time reset delay
0.00
OC2-RTMS-
ORG
0.010 - 50.000
-
OC2 dependent reset time multiplier of ORG
inverse curve
1.000
OC2-k
0.00000 - 500.00000
-
OC2 user original curve coefficient
0.00000
OC2-a
0.00000 - 10.00000
-
OC2 user original curve coefficient
0.00000
OC2-c
0.00000 - 10.00000
-
OC2 user original curve coefficient
0.00000
OC2-kr
0.00000 - 500.00000
-
OC2 user original curve coefficient
0.00000
OC2-b
0.00000 - 10.00000
-
OC2 user original curve coefficient
0.00000
Output
OC2-2fBlk
Non / Block-3P /
Block-PerP
-
OC2 operation block by 2f-detection
Non
OC2-VTFBlk
Non / Block
-
OC2 operation block by VTF
Non
OC2-OPMD
3POR / 2OUTOF3
-
OC2 operation mode
3POR
OC2-UseFor
Trip / Alarm
-
OC2 used for trip or alarm
Trip
OC2-ARCBlk
Non / Block
-
Autoreclose block by OC2
Block
OC3
OC3-Dir
NonDir / Forward /
Reverse
-
OC3 directional characteristic
NonDir
OC3-Angle
0 - 180
deg
OC3 directional characteristic angle
45
OC3-Timer
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
IEEE-MI / IEEE-VI /
IEEE-EI / US-CO2 /
US-CO8 / Original
-
OC3 delay type
DT
DT
OC3
0.02 -
50.00
0.10 -
250.00
A
OC3 threshold (in DT mode)
1.00
5.00
OC3-DPR
10 - 100
%
OC3 drop-out/pick-up ratio
100
TOC3
0.00 - 300.00
s
OC3 operating delay time (in DT mode)
1.00
IEC
OC3
0.02 -
5.00
0.10 -
25.00
A
OC3 threshold (in IDMT mode)
1.00
5.00
OC3-DPR
10 - 100
%
OC3 drop-out/pick-up ratio
100
OC3-TMS-IEC
0.010 - 50.000
-
OC3 time multiplier of IEC inverse curve
1.000
TOC3R
0.00 - 300.00
s
OC3 definite time reset delay
0.00
UK
OC3
0.02 -
5.00
0.10 -
25.00
A
OC3 threshold (in IDMT mode)
1.00
5.00
OC3-DPR
10 - 100
%
OC3 drop-out/pick-up ratio
100
OC3-TMS-UK
0.010 - 50.000
-
OC3 time multiplier of UK inverse curve
1.000
TOC3R
0.00 - 300.00
s
OC3 definite time reset delay
0.00
IEEE
OC3
0.02 -
5.00
0.10 -
25.00
A
OC3 threshold (in IDMT mode)
1.00
5.00
OC3-DPR
10 - 100
%
OC3 drop-out/pick-up ratio
100
OC3-TMS-
IEEE
0.010 - 50.000
-
OC3 time multiplier of IEEE inverse curve
1.000
OC3-Rtimer
DEF / DEP
-
OC3 reset delay type of IEEE
DEF
TOC3R
0.00 - 300.00
s
OC3 definite time reset delay
0.00
OC3-RTMS-
IEEE
0.010 - 50.000
-
OC3 dependent reset time multiplier of IEEE
inverse curve
1.000
US
OC3
0.02 -
5.00
0.10 -
25.00
A
OC3 threshold (in IDMT mode)
1.00
5.00
OC3-DPR
10 - 100
%
OC3 drop-out/pick-up ratio
100
OC3-TMS-US
0.010 - 50.000
-
OC3 time multiplier of US inverse curve
1.000
OC3-Rtimer
DEF / DEP
-
OC3 reset delay type of US
DEF
TOC3R
0.00 - 300.00
s
OC3 definite time reset delay
0.00
OC3-RTMS-US
0.010 - 50.000
-
OC3 dependent reset time multiplier of US
inverse curve
1.000