EasyManua.ls Logo

Toshiba GR200 Series - Page 261

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 238 -
OC (Function ID: 440001)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
ORG
OC3
0.02 -
5.00
0.10 -
25.00
A
OC3 threshold (in IDMT mode)
1.00
5.00
OC3-DPR
10 - 100
%
OC3 drop-out/pick-up ratio
100
OC3-TMS-ORG
0.010 - 50.000
-
OC3 time multiplier of ORG inverse curve
1.000
OC3-Rtimer
DEF / DEP
-
OC3 reset delay type of US
DEF
TOC3R
0.00 - 300.00
s
OC3 definite time reset delay
0.00
OC3-RTMS-
ORG
0.010 - 50.000
-
OC3 dependent reset time multiplier of ORG
inverse curve
1.000
OC3-k
0.00000 - 500.00000
-
OC3 user original curve coefficient
0.00000
OC3-a
0.00000 - 10.00000
-
OC3 user original curve coefficient
0.00000
OC3-c
0.00000 - 10.00000
-
OC3 user original curve coefficient
0.00000
OC3-kr
0.00000 - 500.00000
-
OC3 user original curve coefficient
0.00000
OC3-b
0.00000 - 10.00000
-
OC3 user original curve coefficient
0.00000
Output
OC3-2fBlk
Non / Block-3P /
Block-PerP
-
OC3 operation block by 2f-detection
Non
OC3-VTFBlk
Non / Block
-
OC3 operation block by VTF
Non
OC3-OPMD
3POR / 2OUTOF3
-
OC3 operation mode
3POR
OC3-UseFor
Trip / Alarm
-
OC3 used for trip or alarm
Trip
OC3-ARCBlk
Non / Block
-
Autoreclose block by OC3
Block
OC4
OC4-Dir
NonDir / Forward /
Reverse
-
OC4 directional characteristic
NonDir
OC4-Angle
0 - 180
deg
OC4 directional characteristic angle
45
OC4-Timer
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
IEEE-MI / IEEE-VI /
IEEE-EI / US-CO2 /
US-CO8 / Original
-
OC4 delay type
DT
DT
OC4
0.02 -
50.00
0.10 -
250.00
A
OC4 threshold (in DT mode)
1.00
5.00
OC4-DPR
10 - 100
%
OC4 drop-out/pick-up ratio
100
TOC4
0.00 - 300.00
s
OC4 operating delay time (in DT mode)
1.00
IEC
OC4
0.02 -
5.00
0.10 -
25.00
A
OC4 threshold (in IDMT mode)
1.00
5.00
OC4-DPR
10 - 100
%
OC4 drop-out/pick-up ratio
100
OC4-TMS-IEC
0.010 - 50.000
-
OC4 time multiplier of IEC inverse curve
1.000
TOC4R
0.00 - 300.00
s
OC4 definite time reset delay
0.00
UK
OC4
0.02 -
5.00
0.10 -
25.00
A
OC4 threshold (in IDMT mode)
1.00
5.00
OC4-DPR
10 - 100
%
OC4 drop-out/pick-up ratio
100
OC4-TMS-UK
0.010 - 50.000
-
OC4 time multiplier of UK inverse curve
1.000
TOC4R
0.00 - 300.00
s
OC4 definite time reset delay
0.00
IEEE
OC4
0.02 -
5.00
0.10 -
25.00
A
OC4 threshold (in IDMT mode)
1.00
5.00
OC4-DPR
10 - 100
%
OC4 drop-out/pick-up ratio
100
OC4-TMS-
IEEE
0.010 - 50.000
-
OC4 time multiplier of IEEE inverse curve
1.000
OC4-Rtimer
DEF / DEP
-
OC4 reset delay type of IEEE
DEF
TOC4R
0.00 - 300.00
s
OC4 definite time reset delay
0.00
OC4-RTMS-
IEEE
0.010 - 50.000
-
OC4 dependent reset time multiplier of IEEE
inverse curve
1.000
US
OC4
0.02 -
5.00
0.10 -
25.00
A
OC4 threshold (in IDMT mode)
1.00
5.00
OC4-DPR
10 - 100
%
OC4 drop-out/pick-up ratio
100
OC4-TMS-US
0.010 - 50.000
-
OC4 time multiplier of US inverse curve
1.000

Table of Contents