6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 239 -
OC (Function ID: 440001)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
OC4-Rtimer
DEF / DEP
-
OC4 reset delay type of US
DEF
TOC4R
0.00 - 300.00
s
OC4 definite time reset delay
0.00
OC4-RTMS-US
0.010 - 50.000
-
OC4 dependent reset time multiplier of US
inverse curve
1.000
ORG
OC4
0.02 -
5.00
0.10 -
25.00
A
OC4 threshold (in IDMT mode)
1.00
5.00
OC4-DPR
10 - 100
%
OC4 drop-out/pick-up ratio
100
OC4-TMS-ORG
0.010 - 50.000
-
OC4 time multiplier of ORG inverse curve
1.000
OC4-Rtimer
DEF / DEP
-
OC4 reset delay type of US
DEF
TOC4R
0.00 - 300.00
s
OC4 definite time reset delay
0.00
OC4-RTMS-
ORG
0.010 - 50.000
-
OC4 dependent reset time multiplier of ORG
inverse curve
1.000
OC4-k
0.00000 - 500.00000
-
OC4 user original curve coefficient
0.00000
OC4-a
0.00000 - 10.00000
-
OC4 user original curve coefficient
0.00000
OC4-c
0.00000 - 10.00000
-
OC4 user original curve coefficient
0.00000
OC4-kr
0.00000 - 500.00000
-
OC4 user original curve coefficient
0.00000
OC4-b
0.00000 - 10.00000
-
OC4 user original curve coefficient
0.00000
Output
OC4-2fBlk
Non / Block-3P /
Block-PerP
-
OC4 operation block by 2f-detection
Non
OC4-VTFBlk
Non / Block
-
OC4 operation block by VTF
Non
OC4-OPMD
3POR / 2OUTOF3
-
OC4 operation mode
3POR
OC4-UseFor
Trip / Alarm
-
OC4 used for trip or alarm
Trip
OC4-ARCBlk
Non / Block
-
Autoreclose block by OC4
Block