6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 245 -
Setting of the sensing angle (θ) is configured by the setting [EF1-Angle] with the value of θ set
in the range of 0180°. Figure 2.16-2 shows an example of an angle and a characteristic using
the θ. The operation of the EF element is based upon the following equation.


(2.16-1)

󰇛 󰇜
(2.16-2)


(2.16-3)
where
3Io = residual current
3Vo = residual voltage
3Vo = reference voltage (or polarizing voltage)
φ= lagging angle
θ = EF setting angle
I
EF
= Setting value of the EF element ([EF1-DT] and the others)
EF_Vpol = Setting value of the polarizing voltage ([EF1-Vpol])
Note: In the case of an internal fault, the phase angle is equal to the angle of the zero-
sequence impedance of the system, in a directly-earthed system this value is in
the range of approximately 50° to 90°. The sensing angle θ of the EF element can
be set between 0° to 180°. The minimum voltage necessary to maintain
directionality can be set from 0.5 to 100.0 V.
Figure 2.16-2 Examples of directional characteristic angle (θ)
Forward
Reverse
Forward
Reverse
Forward
Reverse
Forward
Reverse
θ=0°
θ=30°
θ=90°
θ=100°
θ=30°
θ=90°
θ=100°
Vo
3Vo
3Vo
3Vo
Angle line
Forward
Reverse
θ=170°
θ=170°
3Vo