6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 253 -
IEEE-MI
IEEE-VI
IEC-VI
IEC-EI
UK-LTI
ORIGINAL
IEEE-EI
US-C02
US-C08
IEC-NI
DT
EF1_Timer
8000011B63
0.00-300.00s
Block
Block
EF1-EN
On
&
&
≥1
EF1-VTFBlk
EF1-CTFBlk
0
TEF1
t
&
≥1
EF1 PU
ICD-OR
&
≥1
&
&
&
8000011B60
EF1
From ICD
From VTF
800001EBB0 EF1_BLOCK
800001EBB1 EF1_INST_OP
VTF_DETECT
CTF_DETECT
From CTF
Trip
Alarm
EF1-ARCBlk
EF1-Usefor
EF1-OPT
&
&
&
EF1-OPT-TRIP
EF1-OPT-ALARM
EF1-ARC-BLOCK
Block
For DT characteristic
For IDMT characteristic
&
&
&
EF1-2PBlk
Block
To Grouping logic
1
8000011C23
8000011C27
EF1
EF1PU
8000011B64
Figure 2.16-6 Scheme logic for the EF1
Note: The presence of EF1 and EF1PU signals depends on the operation characteristic
defined with setting [EF1_Timer], as shown in Table 2.16-5.
Table 2.16-5 Signal behaviors of PLC monitoring points ‘EF1’ and ‘EF1PU’
PLC monitoring points
Setting [EF1_Timer]
DT
IEC-NT,VI,EI, UK-LTI, IEET-MI,VI,EI, US-CO2,CO8, ORIGINAL
EF1
1
3
EF1PU
2
4
1 : A pick-up signal is generated instantly when the element operates.
2 : No signal due that the PU element is killed. Use EF1 in place of this.
3 : A pick-up signal is generated, but delayed with the IDMT characteristic.
4 : A pick-up signal is generated instantly.
To TRC
EF1-OPT-TRIP
≥1
EF2-OPT-TRIP
EF3-OPT-TRIP
EF4-OPT-TRIP
EF-OPT-TRIP
EF1-OPT-ALARM
≥1
EF2-OPT- ALARM
EF3-OPT- ALARM
EF4-OPT- ALARM
EF-OPT-ALARM
EF1-ARC-BLOCK
≥1
EF2- ARC-BLOCK
EF3- ARC-BLOCK
EF4- ARC-BLOCK
EF-ARC-BLOCK
From EF1 to EF4 logics
EF1-OPT
EF2-OPT
EF3-OPT
EF4-OPT
EF1-OPT
EF2-OPT
EF3-OPT
EF4OPT
To Recording
Figure 2.16-7 Grouping logic for TRC/Recording