EasyManua.ls Logo

Toshiba GR200 Series - Page 290

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 267 -
defines the reset time for the inverse-time-reset characteristic (ref. IEC 60255-151):
󰇛
󰇜


󰇡
󰇢
(2.17-2)
where:
t = time required for the element to reset fully after complete operation (seconds),
I = energizing current (amperes),
Is = threshold setting (amperes),
kr = time required to reset fully after complete operation when the energizing current is
zero
RTMS = time multiplier setting for resetting.
β = constants defining curve.
For setting RTMS for the IEEE standard, the user can use setting [OCN1-RTMS-IEEE]
(incidentally, the default value is 1.000). Similarly, settings [OCN1-RTMS-US] and [OCN1-
RTMS-ORG] are provided for the US standard and the original, respectively (For more
information w.r.t the values for kr and β, see Table 2.17-3; Figure 2.17-4 shows the
characteristic curves).
Table 2.17-3 Constants for inverse-time-reset characteristics
Curve Type
IEC 60255-151
Curve Description
kr
(sec)
β
A
IEC Normal Inverse (IEC-NI)
N/A
N/A
B
IEC Very Inverse (IEC-VI)
N/A
N/A
C
IEC Extremely Inverse (IEC-EI)
N/A
N/A
-
UK Long Time Inverse (UK-LTI)
N/A
N/A
D
IEEE Moderately Inverse (IEEE-MI)
4.85
2
E
IEEE Very Inverse (IEEE-VI)
21.6
2
F
IEEE Extremely Inverse (IEEE-EI)
29.1
2
-
US CO8 inverse (US-CO8)
5.95
2
-
US CO2 short time inverse (US-CO2)
2.261
2
Note: To select the inverse-time-reset characteristic, set [OCN1-Rtimer]=DEP.
Conversely set [OCN1-Rtimer]=DEF to select definite-time-reset characteristic,.
Note: For the setting [OCN1-Rtimer]=DEP (inverse-time-reset), the integrated value will
be reduced in accordance to the magnitude of an energized current, when the
energized current is smaller than the setting [OCN1]. The reducing degree will be
determined with the reset curve characteristics defined in the standards.
Note: For the setting [OCN1-Rtimer]=DEF (definite-time-reset), the integrated value
shall be zero when an energized current is smaller than the setting [OCN1], when
the small energized current is continued for timer setting [TOCN1R]. The
integrated value will not be zero when the energized current does not flow small
for the setting [TOCN1R]. DEF is allowed to set in the IEEE, US, and ORG. DEF is
set unconditionally in the IEC and UK (see Table 2.17-4).

Table of Contents

Related product manuals