6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 691 -
DPSY01 function (Function ID: 511001)
S
R
0.1 50.0 s
[DPSY01-CPW]
PLC
DEV01_CONTROL_REQ
Command Remote-Closing-Control
511001_7002016D08
ILK condition (“Closing”) passed
DPSY01-Close
&
&
1
1
1
&
&
Input
Output
Operate logic in DPSY01
DPSY01_OEC_OK_CS
(511001 8102011E82)
Operate Command with ILK
condition
Operate Command without
condition
&
Operate Command with ILK
condition & synchro-checking
Operate Command with
synchro-checking
&
Assign to BOs
Operate condition
[DPSY01-LGCTRCON]
Fixedlogic
Fixedlogic
[DPSY01-LGCFEXOT]
DPSY01IN_TMP_35
511001 810201EE57
User configurable condition
(PLC#1 connection point)
&
&
DPSY01_OEX_BO §§
(511001 8202011DD3)
To BO connection
[DPSY01-PLSM]*
Var
Fix
Operate Failed
[DPSY01-RST]
ASEQ§ function is in progress
ASEQ_MULTI_SEL
DPSY01_OEC_OK_CSF
(511001 8002011E7F)
DPSY01_EX_FFL ‡‡
(511001 8602011E91)
To Wait for a command
&
&
DPSY01IN_TMP_44
511001 820201EE5E
User configurable condition
(PLC#2 connection point)
1
&
DPSY01_EX_CMP
(511001 8002011E93)
Operate Completed
1.0s- 100.0s
0
t
From SYNCHK
SYNC01-SYN_CLC
(560001 850B011F59)
DPSY01_OEC_OK_CSF
(511001 8002011E7F)
S
R
Detection of state-change in
a device
DPSY01_EX_CMP
(511001 8002011E93)
Figure 4.2-20 Operate ‘Closing’ from the remote-end in DPSY01
††
Note: The ILK function can provide the operation criteria for Closing”.
Note: An operate condition signal is generated in the operate-condition logic (see
Figure 4.2-31) when Fixlogic is set for scheme switch [DPSY01-LGCTRCON]. If an
alternative “operate-condition” is required, it can be programmed by the user and
used to replace the signal generated by the original operated-condition logic. The
alternative “operate-condition” can be connected to the above logic using
connection point #1 “User-configurable condition”. That is, set the scheme switch
[DPSY01-LGCTRCON] to PLC and use “DPSY01IN_TMP_35”.
§Note: The ASEQ function can provide sequential signals for automatic control.
§§Note: The signal “DPSY01_OEX_BO” is issued when Fixlogic is set for scheme switch
[DPSY01-LGCFEXOT]. The “Operate completed” signal can also be issued from
logic programmed by the user, in place of the logic shown in Figure 4.2-20. The
user-programmed logic is connected internally to the signal “Operate completed”,
hence this signal is now generated by the user-programmed logic at connection
point #2 “User-configurable condition”. That is, set the scheme switch [DPSY01-
LGCFEXOT] to PLC and use “DPSY01IN_TMP_44”.