6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 693 -
DPSY01 function (Function ID: 511001)
Assign to BOs
Operate Cmd.
with ILK condition
[DPSY01-PLSM]*
Var
Fix
S
R
Operate Failed
0
t
1.0s- 100.0s
0.1 50.0 s
[DPSY01-RST]
[DPSY01-CPW]
Operation Cmd.
without ILK condition
Operate condition
[DPSY01-LGCTRCON]
Fixedlogic
Fixedlogic
[DPSY01-LGCFEXOT]
DEV01_CONTROL_REQ
Command Remote-On-Control
511001_7002016D08
ILK condition (“Open”) passed
DPSY01-Open
ASEQ function§ is in progress
ASEQ_MULTI_SEL
DPSY01IN_TMP_34
511001 800201EE56
User configurable condition
(PLC#3 connection point)
DPSY01_FEC_OK_CSF
(511001 8002011E7E)
DPSY01_FEC_OK_CSF
(511001 8002011E7E)
&
&
1
&
1
1
&
&
&
DPSY01_FEX_BO §§
(511001 8102011DD0)
DPSY01_EX_FFL
(511001 8602011E91)
Input
Output
Operate logic in DPSY01
To BO connection
To Wait for a command
DPYS01_FEC_OK_CS
(511001 8002011E7E)
&
Detection of state-change in a device
&
DPSY01IN_TMP_44
511001 820201EE5E
User configurable condition
(PLC#2 connection point)
1
&
DPSY01_EX_CMP
(511001 8002011E93)
Operate Completed
Figure 4.2-22 ‘Open’ operate from the remote-end in DPSY01
††
Note: The ILK function can provide the operation criteria for Open”.
Note: An operate condition signal is generated in the operate-condition logic (see
Figure 4.2-31) when Fixlogic is set for scheme switch [DPSY01-LGCTRCON]. If an
alternative “operate-condition” is required, it can be programmed by the user and
used to replace the signal generated by the original operated-condition logic. The
alternative “operate-condition” can be connected to the above logic using
connection point #3 “User-configurable condition”. That is, set the scheme switch
[DPSY01-LGCTRCON] to PLC and use “DPSY01IN_TMP_34”.
§Note: The ASEQ function can provide sequential signals for automatic control.
§§Note: The signal “DPSY01_OEX_BO” is issued when Fixlogic is set for scheme switch
[DPSY01-LGCFEXOT]. The “Operate completed” signal can also be issued from
logic programmed by the user, in place of the logic shown in Figure 4.2-20. The
user-programmed logic is connected internally to the signal “Operate completed”,
hence this signal is now generated by the user-programmed logic at connection
point #2 “User-configurable condition”. That is, set the scheme switch [DPSY01-
LGCFEXOT] to PLC and use “DPSY01IN_TMP_44”.
*Note: The user can set the type of output signal. When Var is set for scheme switch
[DPSY01-PLSM], the output period of the signal is defined by the setting
[DPSY01-CPW]. When Fix is set, the signal ceases when the 43-switch is changed.
††
Note: To identify the input and output signals of the DPSY02 logic, see Table 4.2-16 for