6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 780 -
map the input-point to the Object references having attributes CO and CF. Figure 4.4-16 shows
how to map a signal.
Note: The attribute is defined in the IEC 61850; CO stands for Control and CF
stands for Configuration in the functional constraint (FC).
Table 4.4-6 Mapping signals required for SPCSO object of GGIO3302
Object_reference
Attribute
Type
FC
Signal Number
Signal Name
Ctrl/GGIO3302$SPCSO1$Oper
ctlVal
BOOLEAN
CO
529001 700C016D08
OPTR01_CONTROL_REQ
Ctrl/GGIO3302$SPCSO1$Oper
ctlNum
INT8U
CO
Ctrl/GGIO3302$SPCSO1$Oper
T
Timestamp
CO
Ctrl/GGIO3302$SPCSO1$Oper
Test
BOOLEAN
CO
Ctrl/GGIO3302$SPCSO1$Oper
Check
Check
CO
Ctrl/GGIO3302$SPCSO1$Oper$origin
orCat
orCategory
CO
Ctrl/GGIO3302$SPCSO1$Oper$origin
orIdent
Octet64
CO
Ctrl/GGIO3302$SPCSO1
ctlModel
ctlModel
CF
Ctrl/GGIO3302$SPCSO1
sboClass
sboClass
CF
Check Input
Figure 4.4-16 Input-point mapped for GGIO3302