6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 935 -
TPOS01 function (Function ID: 513001)
Assign to BOs
Operate Cmd.
with ILK condition
S
R
0.1 50.0 s
[TPOS01-CPW]
Operate Cmd.
without ILK condition
Operate condition
[TPOS01-LGCTRCON]
Fixedlogic
Fixedlogic
[TPOS01-LGP1EXOT]
DEV01_CONTROL_REQ
Command Remote-P1-Control
513001_7004016D08
ILK condition (“P1”) passed
TPOS1-P1
TPOS01IN_TMP_27
513001 800401EE56
User configurable condition
(PLC#1 connection point)
TPOS01_P1EC_OK_CSF
(513001 8004011E7E)
&
&
1
&
1
1
&
&
&
TPOS01_P1EX_BO
(5130018104011DD0) §§
Input
Output
Operate logic in TPOS01
To BO connection
TPOS01_P1EC_OK_CS
(5130018004011E81)
[TPOS01-PLSM]*
Fix
Var
Operate Failed
[TPOS01-RST]
ASEQ function§ is in progress
ASEQ_MULTI_SEL
TPOS01_P1EC_OK_CSF
(513001 8004011E7E)
TPOS01_EX_FFL
(513001 8604011E91) ‡‡
To Wait for a command
&
Detection of state-change in a device
&
TPOS01IN_TMP_38
513001 820401EE5E
User configurable condition
(PLC#2 connection point)
1
&
TPOS01_EX_CMP
(5130018004011E93)
Operate Completed
1.0s- 100.0s
0
t
Figure 4.9-27 Operate P1-control from the remote-end in TPOS01
††
Note: The ILK function can provide the operation criteria for P1” control.
Note: An operate condition signal is generated in the operate-condition logic (Figure
4.9-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative “operate-condition” signal is required, it can be programmed by the
user and used to replace the signal the signal generated by the original operate-
condition logic. The alternative “operate-condition” can be connected to the above
logic using connection point #1 “User configurable condition” That is, set the
scheme switch [TPOS01-LGCTRCON] to PLC and use “TPOS01IN_TMP_27”.
§Note: The ASEQ function can provide sequential signals for automatic control.
*Note: The user can set the type of the output signal. When Var is set for scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting
[TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is
changed.
††
Note: To identify the input and output signal-points of the P1-control in the other TPOS
logics, see Table 4.9-15 for PLC#1, Table 4.9-16 for PLC#2 and Table 4.9-20 for the
outputs.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected when
the time set by the [TPOS01-RST] has been reached.
§§Note: The signal “TPOS01-PIEX-BO” is issued when Fixlogic is set for scheme switch