- 935 - 
 
TPOS01  function  (Function  ID:  513001) 
Operate Cmd.   
with ILK† condition 
Operate Cmd.   
without ILK† condition 
Command “Remote-P1-Control” 
ILK† condition (“P1”) passed 
User configurable condition 
(PLC#1 connection point) 
  “TPOS01_P1EC_OK_CSF” 
(513001 8004011E7E) 
  “TPOS01_P1EX_BO” 
(5130018104011DD0) §§ 
  “TPOS01_P1EC_OK_CS” 
(5130018004011E81) 
ASEQ function§” is in progress 
  “TPOS01_P1EC_OK_CSF” 
(513001 8004011E7E) 
  “TPOS01_EX_FFL” 
(513001 8604011E91) ‡‡ 
Detection of state-change in a device 
User configurable condition 
(PLC#2 connection point) 
  “TPOS01_EX_CMP” 
(5130018004011E93) 
 
Figure 4.9-27 Operate ‘P1-control’ from the remote-end in TPOS01
††
 
†Note: The ILK function can provide the operation criteria for “P1” control. 
‡Note: An “operate condition” signal is generated in the operate-condition logic (Figure 
4.9-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an 
alternative “operate-condition” signal is required, it can be programmed by the 
user and used to replace the signal the signal generated by the original operate-
condition logic. The alternative “operate-condition” can be connected to the above 
logic using connection point #1 “User configurable condition” That is, set the 
scheme switch [TPOS01-LGCTRCON] to PLC and use “TPOS01IN_TMP_27”. 
§Note: The ASEQ function can provide sequential signals for automatic control.   
*Note: The user can set the type of the output signal. When Var is set for scheme switch 
[TPOS01-PLSM], the output period of the signal is defined by the setting 
[TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is 
changed. 
††
Note: To identify the input and output signal-points of the P1-control in the other TPOS 
logics, see Table 4.9-15 for PLC#1, Table 4.9-16 for PLC#2 and Table 4.9-20 for the 
outputs. 
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected when 
the time set by the [TPOS01-RST] has been reached. 
§§Note: The signal “TPOS01-PIEX-BO” is issued when Fixlogic is set for scheme switch