EasyManua.ls Logo

Toshiba GR200 Series - Page 972

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 949 -
to be treated as PLC#1 and PLC#2 in Table 4.9-3. Note that the user should set PLC for scheme
switch [TPOS01-LGP2EXOT].
TPOS01 function (Function ID: 513001)
Assign to BOs
Operate Cmd.
with ILK condition
S
R
0.1 50.0 s
[TPOS01-CPW]
Operate Cmd.
without ILK condition
Operate condition
[TPOS01-LGCTRCON]
Fixedlogic
Fixedlogic
[TPOS01-LGP2EXOT]
Command PLC-P2-Control” requiring ILK check
(PLC#3 connection point)
ILK condition (“P2”) passed
TPOS1-P2
TPOS01IN_TMP_28
513001 810401EE57
User configurable condition
(PLC#3 connection point)
TPOS01_P2EC_OK_CSF
(513001 8004011E7F)
&
&
1
&
1
1
&
&
&
TPOS01_P2EX_BO
(513001 8204011DD3) §§
Input
Output
Operate logic in TPOS01
To BO connection
TPOS01_P2EC_OK_CS
(513001 8304011E82)
[TPOS01-PLSM]*
Fix
Var
Operation Failed
[TPOS01-RST]
ASEQ function§ is in progress
ASEQ_MULTI_SEL
TPOS01_P2EC_OK_CSF
(513001 8004011E7F)
TPOS01_EX_FFL
(513001 8604011E91 ‡‡
To Wait for a command
&
Detection of state-change in a device
&
TPOS01IN_TMP_38
513001 820401EE5E
User configurable condition
(PLC#2 connection point)
1
&
TPOS01_EX_CMP
(5130018004011E93)
Operation Completed
1.0s- 100.0s
0
t
DEV01_P2_INTERLOCK
513001 800401EE33
Command PLC-P2-Control” not requiring ILK check
(PLC#4 connection point)
DEV01_P2_COMMAND
513001 800401EE32
Figure 4.9-41 Operate P2-Control by the PLC function in TPOS01
††
Note: The ILK function can provide the criteria foe operation for P2” control.
Note: An operate condition signal is generated in the operate-condition logic (Figure
4.9-44) when Fixlogic is set for scheme switch [TPOS01-LGCTRCON]. If an
alternative “operate-condition programmed by the user is required in place of the
signal generated by the original operate-condition logic, connect the alternative
“operate-condition” to the logic shown in Figure 4.9-41 using connection point #3
“User configurable condition” That is, set the scheme switch [TPOS01-
LGCTRCON] to PLC and use “TPOS01IN_TMP_28”.
§Note: The ASEQ function can provide sequential signals for automatic control.
*Note: The user can set the type of output signal. When Var is set for the scheme switch
[TPOS01-PLSM], the output period of the signal is defined by the setting applied
to [TPOS01-CPW]. When Fix is set, the signal ceases when the 43S or an ES is
changed.
‡‡Note: The “Operate failed” signal is issued when the state-change is not detected until
after reaching the time set by the setting [TPOS01-RST]
§§Note: The signal “TPOS01-PIEX-BO” is issued when Fixlogic is set for [TPOS01-

Table of Contents

Related product manuals