8400 HighLine | Parameter setting & configuration
Function library
Function blocks | L_NSet_1
1002 L Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010
 
14.1.98.1 Main setpoint path
 The signals in the main setpoint path are limited to a value range of ±32767. 
 The signal at nNSet_a is first led via the JOG selection function. 
 A selected JOG value switches the nNSet_a input inactive. Then, the subsequent signal 
conditioning operates with the JOG value.
C00221 0.000 s 999.900 Deceleration time T
if
 for the 
additional setpoint
 • Lenze setting: 0.000 s
C00241
0.00 % 100.00 Hysteresis window for zero detection 
of speed output setpoint (output 
bRfgIEqO)
 • Lenze setting: 0.50 %
C00632/1...3
0.00 % 199.99 Maximum limit values for the speed 
blocking zones
 • Selection of the maximum limit 
values for the blocking zones in 
which the speed must not be 
constant.
 • Lenze setting: 0.00 %
C00633/1...3
0.00 % 199.99 Minimum limit values for the speed 
blocking zones
 • Selection of the minimum limit 
values for the blocking zones in 
which the speed must not be 
constant.
 • Lenze setting: 0.00 %
C00634
Status (bit-coded)
 • Bits that are not listed are 
reserved for future extensions.
Bit 0 No blocking zone active
Bit 1 Blocking zone 1 active
Bit 2 Blocking zone 2 active
Bit 3 Blocking zone 3 active
Bit 4 Jog in blocking zone
Bit 5 MaxLimit active
Bit 6 MinLimit active
C00635
-199.99 % 199.99 nMaxLimit
 • Maximum speed setpoint for 
speed setpoint limitation
 • Lenze setting: 199.99 %
C00636
-199.99 % 199.99 nMinLimit
 • Minimum speed setpoint for 
speed setpoint limitation
 • Lenze setting: -199.99 %
Parameter Possible settings Info