C00607
C00608
Parameter | Name:
C00602 | Resp. to earth fault
Data type: UNSIGNED_8
Index: 23973
d
= 5DA5
h
Response to earth fault in the motor phase(s)
Selection list (Lenze setting printed in bold)
0 No Reaction
1Fault
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00604 | Resp. to device overload (Ixt)
Data type: UNSIGNED_8
Index: 23971
d
= 5DA3
h
Response if the adjustable device utilisation threshold (C00123) is reached.
• The current device utilisation is displayed in C00064
.
Selection list (Lenze setting printed in bold)
0 No Reaction
1Fault
5 Warning
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00606 | Resp. to motor overload (I²xt)
Data type: UNSIGNED_8
Index: 23969
d
= 5DA1
h
Response if the adjustable motor overload threshold (C00120) is reached.
• The current thermal motor load is displayed in C00066
.
Selection list (Lenze setting printed in bold)
0 No Reaction
1Fault
5 Warning
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00607 | Resp. to high freq. DI12/67 reached
Data type: UNSIGNED_8
Index: 23968
d
= 5DA0
h
Response if the maximum input frequency of the actual speed feedback via the digital inputs is reached.
Selection list (Lenze setting printed in bold)
0 No Reaction
1Fault
5 Warning
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00608 | Resp. to maximum torque
Data type: UNSIGNED_8
Index: 23967
d
= 5D9F
h
Response if the maximum torque (C00057) is reached.
Selection list (Lenze setting printed in bold)
0No Reaction
1Fault
5 Warning
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1