Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010 L 525
8400 HighLine | Parameter setting & configuration
System bus "CAN on board"
Process data transfer
 
10.7.3 Transmission type
Process data objects can be transmitted in an event-controlled or time-controlled manner.
The below table shows that it is possible to combine the different methods by means of
logic operations (AND, OR):
 Event-controlled
The PDO is sent when a special device-internal event has occurred, e.g. when the data 
contents of the TPDO have changed or when a transmission cycle time has elapsed
 Synchronous transmission
A TPDO (or RPDO) is transmitted (or received) after the device has received a sync 
telegram (COB-ID 0x80).
 Cyclic transmission
The cyclic transmission of PDOs takes place when the transmission cycle time has 
elapsed. 
 Polled via RTR
A TPDO is transmitted when another device requests it by means of a data request 
telegram (RTR remote transmit request). For this purpose, the data requester (e.g. the 
master) sends the data request telegram with the COB-ID of the TPDO requested to be 
sent. The receiver recognises the RTR and transmits the corresponding PDO.
efesotomasyon.com - Lenze