Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010 L 487
8400 HighLine | Parameter setting & configuration
Diagnostics & error management
Error messages of the operating system
 
CA08: CAN bus stopped [xx.0131.00008]
CA0b: CAN HeartBeatEvent [xx.0131.00011]
CA0F: CAN control word  [xx.0131.00015]
CE1: CAN RPDO1 [xx.0135.00001]
CE2: CAN RPDO2 [xx.0135.00002]
Response (Lenze setting printed in bold) Setting: C00592/4 (; Adjustable response)
: None ; Fault ; Trouble ; TroubleQuickstop ; Warning ; WarningLocked ; Information
Cause Remedy
CAN on board: The device has received the "Stop Remote 
Node" NMT telegram.
Check CAN master (NMT master).
Response (Lenze setting printed in bold) Setting: C00592/5 (; Adjustable response)
: None ; Fault ; Trouble ; TroubleQuickstop ; Warning ; WarningLocked ; Information
Cause Remedy
CAN on board: Cyclic node monitoring
 • Being a Heartbeat consumer, the device has not 
received a Heartbeat telegram from Heartbeat 
producer 1 ... 15 within the defined time.
 • The current statuses of the Heartbeat producers are 
displayed in C00345/1...15
.
 • Reactivate Heartbeat producers by mains switching, 
restarting the controller, or a CAN Reset Node.
 • Reparameterise CAN Heartbeat producer time or 
switch off consumer monitoring and reset error 
status if latched.
System bus "CAN on board": Heartbeat protocol
Response (Lenze setting printed in bold) Setting: C00594/2 (; Adjustable response)
; None : Fault ; Trouble ; TroubleQuickstop ; Warning  WarningLocked  Information
Cause Remedy
Bit 14 ("SetFail") of the wCANCtrl control word of the 
LS_DriveInterface
 system block has been set.
Trace back signal source on the CAN bus that sets bit 14 
("SetFail").
Response (Lenze setting printed in bold) Setting: C00593/1 (; Adjustable response)
: None ; Fault ; Trouble ; TroubleQuickstop ; Warning ; WarningLocked ; Information
Cause Remedy
CAN on board: Time monitoring for RPDO1 has tripped.
 • RPDO1 has not been received within the monitoring 
time set in C00357/1
 or was faulty.
 • Set the correct telegram length at the CAN master 
(transmitter).
 • Eliminate electrical interference (e.g. EMC).
 • Adjust monitoring time in C00357/1
 or switch off 
time monitoring.
Response (Lenze setting printed in bold) Setting: C00593/2 (; Adjustable response)
: None ; Fault ; Trouble ; TroubleQuickstop ; Warning ; WarningLocked ; Information
Cause Remedy
CAN on board: Time monitoring for RPDO2 has tripped.
 • RPDO1 has not been received within the monitoring 
time set in C00357/2 
 or was faulty.
 • Set the correct telegram length at the CAN master 
(transmitter).
 • Eliminate electrical interference (e.g. EMC).
 • Adjust monitoring time in C00357/2 
 or switch off 
time monitoring.