Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010 L 673
8400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00593
C00593
C00594
Parameter | Name:
C00593 | Resp. to CANx_IN monitoring
Data type: UNSIGNED_8
Index: 23982
d
= 5DAE
h
Configuration of monitoring of the CAN interface (group 2)
System bus "CAN on board"
Selection list
0 No Reaction
1Fault
2Trouble
3 TroubleQuickStop
4 WarningLocked
5 Warning
6 Information
Subcodes Lenze setting Info
C00593/1 0: No Reaction Response if the monitoring time set in C00357/1
for the
reception of the PDO CAN1_IN is exceeded.
C00593/2 0: No Reaction Response if the monitoring time set in C00357/2
for the
reception of the PDO CAN2_IN is exceeded.
C00593/3 0: No Reaction Response if the monitoring time set in C00357/3
for the
reception of the PDO CAN3_IN is exceeded.
; Read access ; Write access CINH PLC STOP No transfer ; COM MOT Scaling factor: 1
Parameter | Name:
C00594 | Resp. to control word error
Data type: UNSIGNED_8
Index: 23981
d
= 5DAD
h
Configuration of monitoring of the device control
Selection list
0 No Reaction
1Fault
2Trouble
3 TroubleQuickStop
5 Warning
Subcodes Lenze setting Info
C00594/1 1: Fault Response if error bit 14 in the CAN control word is set.
C00594/2 1: Fault Response if error bit 14 in the MCI control word is set.
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1