14.1.54 L_Curve_1
This FB can optionally display a characteristic function or a curve function y=f(x), the X axis
being the input signal and the Y axis being the output signal.
A limitation of the input value can be set in C00961/1
(upper limit) and C00961/2
(lower limit).
The output value is internally limited to ±199.99 %. If a limitation of the output value
is active, bLimit is set to TRUE.
Inputs
Outputs
Parameter
Identifier
Data type
Information/possible settings
nIn_a
INT
Input value (x)
• ±16384 ≡ ±100 %
• A limitation of the input value can be set in C00961/1 (upper limit) and C00961/
2 (lower limit).
Identifier
Data type
Value/meaning
nOut_a
INT
Output value (y)
• ±16384 ≡ ±100 %
• Internal limitation to ±32767 (±199.99 %)
bLimit
BOOL
"Limitation active" status signal
TRUE The output value is limited to ±199.99 %.
Parameter Possible settings Info
C00960
Function selection
0 nOut_a = 0 (FB deactivated) Lenze setting
1 nOut_a = nIn_a
2 nOut_a = f(x) In preparation!
Function 2: nOut_a = f(x)
3 nOut_a = f(table) Function 3: nOut_a = f(table)
C00961/1 -199.99 % 199.99 Upper limit for input value
• Lenze setting: 199.99 %
C00961/2
-199.99 % 199.99 Lower limit for input value
• Lenze setting: -199.99 %