Firmware 05.00 - DMS 4.2 EN - 02/2010 L 117
8400 HighLine | Parameter setting & configuration
Motor control (MCTRL)
V/f characteristic control (VFCplus)
5.4.2.1 Adapting the V/f base frequency
The V/f base frequency (C00015
) determines the slope of the V/f characteristic and has
considerable influence on the current, torque, and power performance of the motor.
The setting in C00015
applies to all permitted mains voltages.
Mains fluctuations or fluctuations of the DC-bus voltage (operation in generator mode)
do not need to be considered when the V/f base frequency is set. They are
automatically compensated for by the internal mains voltage compensation of the
device.
Depending on the setting in C00015
, it may be required to adapt the reference speed
(C00011
) to traverse the entire speed range of the motor.
The V/f base frequency is automatically calculated from the stored motor nameplate
data by the motor parameter identification:
[5-5] Calculation of the V/f base frequency
Typical values of the V/f base frequency
U
FU
: Mains voltage 400 V or 230 V
U
ratedmot
: Rated motor voltage depending on the connection method
f
rated
: Rated motor frequency
C00015 [Hz]
U
FI
[V]
U
Ratedmot
[V]
----------------------------------
f
Rated
Hz=
Drive controller with 400 V mains connection
Motor voltage [V] Motor frequency [Hz] Motor connection V/f base frequency
(C00015)
230 / 400 50 50 Hz
220 / 380 50 52.6 Hz
280 / 480 60 50 Hz
400 / 690
400
50
50
50 Hz
230 / 400
280 / 480
400
50
60
87
87 Hz
220 / 380 50 90.9 Hz
Drive controller with 230 V mains connection
Motor voltage [V] Motor frequency [Hz] Motor connection V/f base frequency
(C00015)
230 50 50 Hz
220 / 380 50 52.3 Hz