8400 HighLine | Parameter setting & configuration
Commissioning
Safety instructions with regard to commissioning
36 L Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010
3.2 Safety instructions with regard to commissioning
3.2.1 General safety instructions
In order to prevent injury to persons or damage to material assets
before connecting the mains voltage, check
– The wiring for completeness, short circuit, and earth fault
– The "emergency stop" function of the entire system
– The motor circuit configuration (star/delta) must be adapted to the output voltage
of the controller
– The in-phase connection of the motor
– The direction of rotation or the encoder (if available)
The setting of the most important drive parameters before enabling the controller:
– Is the V/f rated frequency adapted to the motor circuit configuration?
– Are the drive parameters relevant for your application set correctly?
– Is the configuration of the analog and digital inputs and outputs adapted to the
wiring?
3.2.2 Safety instructions with regard to motor operation
Danger!
• For thermal reasons, continuous operation of self-ventilated motors at a low
field frequency and rated motor current is not permissible. If required, a
motor temperature monitoring should be activated with C00585
Motor temperature monitoring (PTC) ( 201)
Brake resistor monitoring (I2xt)
( 202)
• C00015 must be used to select 87 Hz operation if a delta-connected
asynchronous motor (nameplate data: 400 V
/230 V
) is to be operated in
conjunction with a drive controller for a mains voltage of 400 V.