Firmware 05.00 - DMS 4.2 EN - 02/2010 L 505
8400 HighLine | Parameter setting & configuration
System bus "CAN on board"
Possible settings via DIP switch
10.2 Possible settings via DIP switch
[10-1] DIP switch
Lenze setting: All DIP switches are in the "OFF" position
Tip!
The current DIP switch settings are displayed in code C00349
.
Bit 15 indicates that the setting of the DIP switches has been accepted when the
device or the 24V supply has been switched on.
10.2.1 Activating the bus terminating resistor
The CAN bus must be terminated between CAN low and CAN high at the first and last
physical node each by a resistor (120 Ω). The 8400 controller is provided with an integrated
bus terminating resistor, which can be activated via the unlabelled DIP switch.
DIP switch position ("R"):
OFF = bus terminating resistor is inactive
ON = bus terminating resistor is active
Switch position:
The following can be set via the front panel DIP
switches:
Bus terminating resistor
Switch: "R"
Baud rate
Switch: "a" ... "d"
Node address
Switch: "1" ... "64"
cd ba
64
32
168
421
R
OFF
ON
Note!
The DIP switch settings are accepted if at least one DIP switch setting for the
node address (1 ... 63) is unequal zero when the device or the external 24 V
supply is switched on.
If the DIP switch setting is zero when the device or the 24 V supply is switched
on, the setting of the baud rate and node address are read out of the
parameter set/parameter.