8400 HighLine | Parameter setting & configuration
I/O terminals
Electrical data
252 L Firmware 05.00 - DMS 4.2 EN - 02/2010
6.6 Electrical data
Digital input terminals
Terminal Use Electrical data
X5/DI1
..
X5/DI7
Digital input 1 ... 7 LOW level: 0 ... +5 V
HIGH level: +15 ... +30 V
Input current: 8 mA per input (at 24 V)
Electric strength of external
voltage
Max. ± 30 V, permanent
Input impedance: 3.3 kΩ (2.5 Ω ... 6 kΩ)
Max. input frequency: 100 kHz (DI1/DI2)
10 kHz (DI6/DI7)
Processing cycle: 1 ms (can be changed by filtering via the
software)
X5/24E External supply of
the device and the
following terminals:
DI1 ..... DI7
•RFR, and
control board and
bus module
DC 19.2 ... 28.8 V, IEC 61131-2, SELV/PELV
Current consumption 0.6 A
In case of polarity reversal: No function and no destruction
X5/24I Internal supply of the
terminals
DI1 ..... DI7
•RFR
Max. output current: 50 mA
X5/RFR Controller enable See digital inputs
X5/GIO Reference potential (digital ground)
X5
DI3
DI2
DI4DI5DI6
DI7
GI
24E
24I
DI1
RFR