8400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00820
708 L Firmware 05.00 - DMS 4.2 EN - 02/2010
C00820
C00821
C00822
Parameter | Name:
C00820 | L_DigitalLogic_1: Function
Data type: UNSIGNED_8
Index: 23755
d
= 5CCB
h
FB L_DigitalLogic_1: Selection of the internal logic interconnection
Selection list (Lenze setting printed in bold) Info
0bOut = 0
1bOut = 1
2 bOut = bIn1 AND bIn2 AND bIn3
3 bOut = bIn1 OR bIn2 OR bIn3
4 bOut = f (truth table) The truth table parameterised in C00821
is used.
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00821 | L_DigitalLogic_1: Truth table
Data type: UNSIGNED_8
Index: 23754
d
= 5CCA
h
FB L_DigitalLogic_1: Parameterisation of the truth table
Selection list
0False
1True
Subcodes Lenze setting Info
C00821/1 0: FALSE bOut for bIn1=0 / bIn2=0 / bIn3=0
C00821/2 0: FALSE bOut for bIn1=1 / bIn2=0 / bIn3=0
C00821/3 0: FALSE bOut for bIn1=0 / bIn2=1 / bIn3=0
C00821/4 0: FALSE bOut for bIn1=1 / bIn2=1 / bIn3=0
C00821/5 0: FALSE bOut for bIn1=0 / bIn2=0 / bIn3=1
C00821/6 0: FALSE bOut for bIn1=1 / bIn2=0 / bIn3=1
C00821/7 0: FALSE bOut for bIn1=0 / bIn2=1 / bIn3=1
C00821/8 0: FALSE bOut for bIn1=1 / bIn2=1 / bIn3=1
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00822 | L_DigitalLogic_2: Function
Data type: UNSIGNED_8
Index: 23753
d
= 5CC9
h
FB L_DigitalLogic_2: Selection of the internal logic interconnection
Selection list (Lenze setting printed in bold) Info
0bOut = 0
1bOut = 1
2 bOut = bIn1 AND ... bIn3
3 bOut = bIn1 OR ... bIn3
4 bOut = f (truth table) The truth table parameterised in C00823
is used.
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1