8400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00354
644 L Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010
C00354
C00355
Parameter | Name:
C00354 | COBID
Data type: UNSIGNED_32
Index: 24221
d
= 5E9D
h
Setting of the default COBID according to CANopen
• A change of the COBID will only become effective after a CAN reset node.
System bus "CAN on board"
Setting range (min. hex value | max. hex value)
0x00000000 0xFFFFFFFF
Value is bit-coded: Info
Bit 0 COBID Bit0 • Bit 0 ... 10: COB-ID
• Bit 11 ... 30: Reserved
• Bit 31: PDO invalid (is not transmitted)
... ...
Bit 31 PDO invalid
Subcodes Lenze setting Info
C00354/1 513 COBID CAN1_IN
C00354/2 385 COBID CAN1_OUT
C00354/3 769 COBID CAN2_IN
C00354/4 641 COBID CAN2_OUT
C00354/5 1025 COBID CAN3_IN
C00354/6 897 COBID CAN3_OUT
; Read access ; Write access CINH PLC STOP No transfer ; COM MOT
Parameter | Name:
C00355 | Active COBID
Data type: UNSIGNED_16
Index: 24220
d
= 5E9C
h
Display of the COBID of the PDOs that is active in the CAN stack
System bus "CAN on board"
Display range (min. value | unit | max. value)
0 2047
Subcodes Info
C00355/1 Active COBID CAN1_IN
C00355/2 Active COBID CAN1_OUT
C00355/3 Active COBID CAN2_IN
C00355/4 Active COBID CAN2_OUT
C00355/5 Active COBID CAN3_IN
C00355/6 Active COBID CAN3_OUT
; Read access Write access CINH PLC STOP ; No transfer ; COM MOT Scaling factor: 1