8400 HighLine | Parameter setting & configuration
Device control (DCTRL)
Controller commands
70 L Firmware 05.00 - DMS 4.2 EN - 02/2010
4.1.2 Load all parameter sets
The C00002/6
= "1: On / start" controller command reloads all parameter settings from the
memory module to the controller.
Can only be executed if the controller is inhibited; otherwise, the feedback C00002/
6 = "6: No access - controller inhibit" will be returned.
All parameter changes which have been carried out after the last time the parameter
set was saved will be lost!
This controller command has an effect on the settings of the parameters of the
operating system, application and module.
How to load the parameter settings from the memory module:
1. If the controller is enabled, it must be inhibited, e.g. by executing the "Enable/
Inhibit controller" controller command (C00002/16
= "0: Off / ready").
2. Execute the "Load all parameter sets" controller command:
C00002/6
= "1: On / start"
The loading process may take a couple of seconds. After the controller command
has been called in C00002/6
, dynamic status information ("Work in progress 20%"
"Work in progress 40%" "Work in progress 60%", etc.) is returned.