Firmware 05.00 - DMS 4.2 EN - 02/2010 L 649
8400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00385
C00385
C00386
C00400
Parameter | Name:
C00385 | CAN node addr. HeartBeat producer
Data type: UNSIGNED_8
Index: 24190
d
= 5E7E
h
The subcodes represent the nodes to be monitored by heartbeat.
System bus "CAN on board": Heartbeat protocol
Setting range (min. value | unit | max. value)
0 127
Subcodes Lenze setting Info
C00385/1 0 CAN node address HeartBeat producer 1 ... 15
C00385/...
C00385/15
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00386 | CAN HeartBeat ConsumerTime
Data type: UNSIGNED_16
Index: 24189
d
= 5E7D
h
The subcodes represent the nodes to be monitored by heartbeat.
System bus "CAN on board": Heartbeat protocol
Setting range (min. value | unit | max. value)
0 ms 60000
Subcodes Lenze setting Info
C00386/1 0 ms ConsumerTime HeartBeat producer 1 ... 15
C00386/...
C00386/15
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00400 | LS_PulseGenerator
Data type: UNSIGNED_16
Index: 24175
d
= 5E6F
h
Time setting of the pulse to be output by the SB LS_PulseGenerator
Setting range (min. value | unit | max. value)
0 ms 60000
Subcodes Lenze setting Info
C00400/1 1000 ms Length of LOW level (dead time)
C00400/2 1000 ms Length of HIGH level
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1