8400 HighLine | Parameter setting & configuration
Diagnostics & error management
Error messages of the operating system
484 L Firmware 05.00 - DMS 4.2 EN - 02/2010
OC15: Cross current controller limitation [xx.0123.00097]
OC16: Torque controller limitation [xx.0123.00098]
FC1: Field controller limitation [xx.0123.00099]
OC6: I2xt overload - motor [xx.0123.00105]
LP1: Motor phase failure [xx.0123.00145]
Response (Lenze setting printed in bold) Setting: C00570/2 (; Adjustable response)
: None ; Fault Trouble TroubleQuickstop ; Warning WarningLocked Information
Cause Remedy
Cross current controller limitation is active. Observe load requirements.
Correct dimensioning or reduce setpoint generation
dynamics if necessary.
Check parameter setting of the current controller
with regard to the motor controllers (e.g. reduce Vp).
Motor control
Response (Lenze setting printed in bold) Setting: C00570/3 (; Adjustable response)
: None ; Fault Trouble TroubleQuickstop ; Warning WarningLocked Information
Cause Remedy
Actuator limitation according to speed controller. Observe load requirements.
Correct dimensioning or reduce setpoint generation
dynamics if necessary.
Motor control
Response (Lenze setting printed in bold) Setting: C00570/4 (; Adjustable response)
: None ; Fault Trouble TroubleQuickstop ; Warning WarningLocked Information
Cause Remedy
The output of the field controller has reached its
maximum limit value. The drive is at the torque limit in
the field weakening range.
Observe load requirements.
Correct dimensioning or reduce setpoint from the
field weakening range if necessary.
Motor control
Response (Lenze setting printed in bold) Setting: C00606 (; Adjustable response)
; None ; Fault Trouble TroubleQuickstop : Warning WarningLocked Information
Cause Remedy
Thermal overload of the motor. Observe load requirements.
Correct dimensioning if necessary.
In case of VFCplus operation: Check Vmin boost
(C00016
).
Set Vmin boost
Response (Lenze setting printed in bold) Setting: C00597 (; Adjustable response)
: None ; Fault Trouble TroubleQuickstop ; Warning WarningLocked Information
Cause Remedy
Motor phase failure - power section
This error message is displayed if a motor phase
carries less current of one half-wave than set in
C00599
.
Check the motor connections and the corresponding
plug connector on the device and, if necessary, the
motor terminal box.
Check the trigger threshold C00599.