Firmware ≤ 05.00 - DMS 4.2 EN - 02/2010 L 623
8400 HighLine | Parameter setting & configuration
Parameter reference
Parameter list | C00169
C00169
C00170
C00171
C00173
Parameter | Name:
C00169 | Logbook setting
Data type: UNSIGNED_16
Index: 24406
d
= 5F56
h
Configuration which message types are to be logged in the logbook.
Setting range (min. hex value | max. hex value) Lenze setting
0x0000 0xFFFF 0x067E (decimal: 1662)
Value is bit-coded: (; =bit set)
Bit 0 Reserved
Bit 1 ; Log entry: Fault
Bit 2 ; Log entry: Trouble
Bit 3 ; Log entry: TroubleQuickstop
Bit 4 ; Log entry: WarningLocked
Bit 5 ; Log entry: Warning
Bit 6 ; Log entry: Information
Bit 7 Reserved
Bit 8 Reserved
Bit 9 ; Activation: Error counter
Bit 10 ; Activation: Log line refresh
Bit 11 Reserved
Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
Bit 15 Reserved
; Read access ; Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00170 | Current error
Data type: UNSIGNED_32
Index: 24405
d
= 5F55
h
Display of the internal error number for the currently pending error
Display range (min. value | unit | max. value)
0 4294967295
; Read access Write access CINH PLC STOP ; No transfer COM MOT Scaling factor: 1
Parameter | Name:
C00171 | Logbook access index
Data type: UNSIGNED_8
Index: 24404
d
= 5F54
h
This code is for device-internal use only and must not be written to by the user!
Parameter | Name:
C00173 | Mains voltage
Data type: UNSIGNED_8
Index: 24402
d
= 5F52
h
Selection of the mains voltage for operating the device.
Selection list (Lenze setting printed in bold) Info
0 3ph 400V / 1ph 230V 3-phase 400 V or 1-phase 230 V
1 3ph 440V / 1ph 230V 3-phase 440 V or 1-phase 230 V
2 3ph 480V / 1ph 230V 3-phase 480 V or 1-phase 230 V
3 3ph 500V / 1ph 230V 3-phase 500 V or 1-phase 230 V
4 3ph 400V / 1ph 115V 3-phase 400 V or 1-phase 115 V
; Read access ; Write access ; CINH PLC STOP No transfer COM MOT Scaling factor: 1