Function blocks | L_SampleHold_1
14.1.125 L_SampleHold_1
This FB can store a signal.
The saved value is also available after mains switching.
Inputs
Outputs
Function
When bLoad = TRUE, the nIn_a signal is switched to nOut_a.
When bLoad = FALSE, the last-valid value is saved and output at nOut_a. A signal
change at nIn_a does not cause a change at nOut_a.
Behaviour after mains switching
The last-loaded value is permanently stored after switching of the supply voltage and
reloaded after restart.
In order that the saved value is not immediately overwritten with the current input
signal at nIn after restart, bLoad must be set to FALSE at restart.
Identifier
Data type
Information/possible settings
nIn_a
INT
Input signal
bLoad
BOOL
Save input signal
FALSE The last-valid value at nIn is saved and output to nOut. A signal
change at nIn does not cause a change at nOut.
TRUE The nOut output provides dnIn.
Identifier
Data type
Value/meaning
nOut
INT
Output signal
/B6DPSOH+ROGB
E/RDG
Q,QBD
6+
Q2XWBD