Parameter list | C00517
C00517
Parameter | Name:
C00517 | User menu
Data type: INTEGER_32
Index: 24058
d
= 5DFA
h
When a system is installed, parameters must be changed time and again until the system runs satisfactorily. The
user menu of a device serves to create a selection of frequently used parameters to be able to access and change
these parameters quickly.
•Format: <code number>,<subcode number>
• For setting "0.000" no entry is displayed in the user menu.
Setting range (min. value | unit | max. value)
0.000 16000.000
Subcodes Lenze setting Info
C00517/1 51.000 C00051
: Display of actual speed value
C00517/2 53.000 C00053
: Display of DC-bus voltage
C00517/3 54.000 C00054
: Display of motor current
C00517/4 61.000 C00061
: Display of heatsink temperature
C00517/5 137.000 C00137
: Display of device state
C00517/6 0.000 User menu: entry 6
C00517/7 0.000 User menu: entry 7
C00517/8 11.000 C00011
: Reference speed
C00517/9 39.001 C00039/1
: Fixed setpoint 1
C00517/10 39.002 C00039/2
: Fixed setpoint 2
C00517/11 12.000 C00012
: Acceleration time - main setpoint
C00517/12 13.000 C00013
: Deceleration time - main setpoint
C00517/13 15.000 C00015
: V/f base frequency
C00517/14 16.000 C00016
: Vmin boost
C00517/15 22.000 C00022
: Imax in motor mode
C00517/16 120.000 C00120
: Motor overload threshold (I
2
xt)
C00517/17 87.000 C00087
: Rated motor speed
C00517/18 99.000 C00099
: Display of firmware version
C00517/19 200.000 C00200
: Display of firmware product type
C00517/20 0.000 User menu: entry 20
C00517/21 0.000 User menu: entry 21
C00517/22 0.000 User menu: entry 22
C00517/23 0.000 User menu: entry 23
C00517/24 0.000 User menu: entry 24
C00517/25 0.000 User menu: entry 25
C00517/26 0.000 User menu: entry 26
C00517/27 0.000 User menu: entry 27
C00517/28 0.000 User menu: entry 28
C00517/29 0.000 User menu: entry 29
C00517/30 0.000 User menu: entry 30
C00517/31 0.000 User menu: entry 31
C00517/32 0.000 User menu: Entry 32
; Read access ; Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1000